HT instruments SOLAR300N User Manual
Page 141

SOLAR300 - SOLAR300N
EN - 139
The following keys are active on this page:
The
F1 key (or the PAG item on the display) advances to the following page
of saved values.
The
ESC key (or the smart icon on the display) to exit the function and go
back to the “Recording analysis” page (Fig. 181).
In this page, the following symbols are used:
V12 Phase L1 - Phase L2 Voltage.
V23 Phase L2 - Phase L3 Voltage.
V31 Phase L3 - Phase L1 Voltage.
Inv% % value of the Negative sequence unbalance.
Omo%
% value of the Zero sequence
unbalance.
SEQ Phase
sequence:
”123” => Correct.
”132” => Not correct.
”023” => No Voltage on B1.
”103” => No Voltage on B2.
”120” => No Voltage on B3.
”100” => No Voltage on B2 and B3.
”020” => No Voltage on B1 and B3.
”003” => No Voltage on B1 and B2.
Hz Frequency.
I1
Current on phase L1.
I2
Current on phase L2.
I3
Current on phase L3.
Fig. 227: Page 1/4 of numeric values for Aron system
The following keys are active on this page:
The
F1 key (or the PAG item on the display) advances to the following page
of saved values.
The
ESC key (or the smart icon on the display) to exit the function and go
back to the “Recording analysis” page (Fig. 181).
In this page, the following symbols are used:
Patt System total active power.
Preatt Total reactive power.
Papp Total apparent power.
Pf
Total power factor.
CosPhi
System total CosPhi.
CosPhi represents the theoretical limit value which
can be reached by the Power factor if all harmonics
are eliminated from the electrical system. For
dimensioning a power factor correction system,
reference is usually made to the CosPhi parameter
value.
Fig. 228: Page 2/4 of numeric values for Aron system