beautypg.com

Edwards Signaling 5541M-Y6 User Manual

Page 28

background image

P/N 3100471 ISSUE 3

PAGE 28

Maximum signal loss allowed [1]

5532M Amplifier Circuit Maximum Wire Length Calculation

Use this worksheet to determine the maximum wire length of
an Audio Amplifier appliance circuit. Fill in one worksheet for
each Audio Amplifier appliance circuit connected to the panel.

Wire length matrix

Wire lengths in the following table are based on a voltage drop
of 1.6 volts or 15% of the Panel's audio output End of line
appliance.

Wire resistance per 1000 ft/pair x 2 [2]
(2x the number in note 2)

Total operating current required

Maximum wire length

V

x

1000

/

ohms

ohms

/

A

ft

Current

Maximum wire length (ft)

required (A)

18 AWG

16 AWG

14 AWG

12 AWG

0.25

584

950

1460

2170

0.50

292

474

730

1084

0.75

194

316

486

722

1.00

146

236

364

542

1.25

116

190

292

434

1.50

92

158

242

362

Notes

[1] 1.6V

rms

loss in order to produce 75 dBA minimum.

[2] Use 1.6 for 12 AWG and 2.5 sq mm wire, 2.6 for 14 AWG and 1.5 sq mm wire, 4.2 for 16 AWG and 1.0 sq mm wire and 6.6

for 18 AWG and 0.75 sq mm wire