Appendix A - Calculations

Battery calculation worksheet

Use this worksheet to determine the minimum amperage capacity
required for the panel's standby power source. You can obtain
operating current requirements for amplifier units from their re-
spective installation sheets. For 5532M series amplifiers, the audio
signal draw for each audio amplifier is approximately 2 mA at
470 Hz.

NOTE:

Base panel includes the main controller board with no
system audio output loading and only EOL resistors.

Standby current: Master and Satellite - 230 mA

Alarm current: Master and Satellite - 215 mA

NOTE:

Alarm current with no amplifier loading is less because EOL
resistor path is opened during alarm condition and closed
during supervision.

Base Millennium System Master
Panel [1]

RPU Current draw
(See Form A)

Audio Amplifier Loading
(See Form B)

Total Current

Required standby and alarm time

x

Standby

Current (mA)

0

Standby time
24 or 60 hour

mAh

+

Alarm

Current (mA)

0

Alarm time

5 min = 0.083
10 min = 0.167
15 min = 0.250
30 min = 0.500

mAh

=

mAh

/1000

Ah

x 1.2

Battery amp hour total =

+ 0.25

Minimum battery size [2] =

Ah

Standby

Qty x Standby

Paging

Qty x Paging

Product

Quantity

current

current (mA)

current

current (mA)

(mA)

Form A

5542RPU

5

22

Total RPU
Current [2]

[1] See Appendix C for the maximum number of amplifiers supported by the panel.
[2] RPU power supplied by panel cannot exceed 0.55A (paging current). If more than 0.55A is required, you must reduce number of RPU

devices supplied by the panel.

x