Technical data, 240vac models – Sterling RT User Manual
Page 9

8
SV01H
Technical Data
2.3
Ratings
120V / 240VAC Models
Mains = 120V Single Phase (1/N/PE) (90...132V), 240V Single Phase (2/PE) (170...264V); 48...62Hz
Type
Power
Mains Current
Output Current
Heat Loss (Watts)
Hp
kW
120V
A
240V
A
Cont (I
n
)
A
Max I
%
N1/IP31
N4X/IP65
No filter
N4X/IP65
W/ filter
ESV251--1S--
0.33
0.25
6.8
3.4
1.7
200
24
ESV371--1S--
0.5
0.37
9.2
4.6
2.4
200
32
32
ESV751--1S--
1
0.75
16.6
8.3
4.2
200
52
41
ESV112--1S--
1.5
1.1
20
10.0
6.0
200
74
74
NOTES:
Output Current: The Output Current Maximum (%) is a percentage of the Output Current Continuous Amps (In) rating
and is adjustable in parameter P171.
240VAC Models
Mains = 240V Single Phase (2/PE) (170...264V); 48...62Hz
Type
Power
Mains Current
Output Current
Heat Loss (Watts)
Hp
kW
240V
A
Cont (I
n
)
A
Max I
%
N1/IP31
N4X/IP65
No filter
N4X/IP65
W/ filter
ESV251--2S--
0.33
0.25
3.4
1.7
200
20
ESV371--2S--
0.5
0.37
5.1
2.4
200
30
ESV751--2S--
1
0.75
8.8
4.2
200
42
ESV112--2S--
1.5
1.1
12.0
6.0
200
63
ESV152--2S--
2
1.5
13.3
7.0
200
73
ESV222--2S--
3
2.2
17.1
9.6
200
97
240V Single Phase (2/PE) (170...264V), 240V Three Phase (3/PE) (170...264V); 48...62Hz
Type
Power
Mains Current
Output Current
Heat Loss (Watts)
Hp
kW
1~ (2/PE)
A
3~ (3/PE)
A
Cont (I
n
)
A
Max I
%
N1/IP31
N4X/IP65
No filter
N4X/IP65
W/ filter
ESV371--2Y--
0.5
0.37
5.1
2.9
2.4
200
27
26
ESV751--2Y--
1
0.75
8.8
5.0
4.2
200
41
38
ESV112--2Y--
1.5
1.1
12.0
6.9
6.0
200
64
59
ESV152--2Y--
2
1.5
13.3
8.1
7.0
200
75
69
ESV222--2Y--
3
2.2
17.1
10.8
9.6
200
103
93