Commissioning – Sterling RT User Manual
Page 41

40
SV01H
Commissioning
Code
Possible Settings
IMPORTANT
No.
Name
Default Selection
P 1
Network Baud Rate
0 2400 bps
Modbus
1 4800 bps
2 9600 bps
3 19200 bps
0
0 9600 bps
Lecom
1 4800 bps
2 2400 bps
3 1200 bps
4 19200 bps
P 2
Network Data Format
0 8, N, 2
Modbus Only
1 8, N, 1
2 8, E, 1
3 8, O, 1
Network Control
Level
0
0 Monitor Only
Lecom Only
1 Parameter Programming
2 Programming and Setpoint Control
3 Full Control
P
Network Powerup
Start Status
0
0 Quick Stop
Lecom Only
1 Controller Inhibit
p
Network Timeout
0
0.0 - 300.0 seconds
Modbus
0 - 65000 milliseconds
Lecom
P
Network Timeout
Action
4
0 No action
Modbus
1 Stop (P111)
2 Quick Stop
3 Controller Inhibit
4 Trip Fault, F.nF1
0
0 No action
Lecom
1 Controller Inhibit
2 Quick Stop
3 Trip Fault, F.nF1
P 7
Network Messages
Received
Read-Only: 0 - 9999
Valid network messages received
NOTE: When the number of messages exceeds 9999, the counter resets and resumes
counting from 0.