beautypg.com

Commissioning – Sterling RT User Manual

Page 29

background image

28

SV01H

Commissioning

Code

Possible Settings

IMPORTANT

No.

Name

Default Selection

NOTE
• When input is activated, settings 1...7 override P101
• When TB-13A...TB-13D are configured for Auto References other than MOP, TB-13D overrides TB-13C, TB-13C

overrides TB-13B and TB-13B overrides TB-13A. Any other Auto Reference will have priority over MOP.

• Settings 10...14 are only valid in Terminal Strip mode (P100 = 1, 4, 5, 6)
• If Start/Run/Jog Forward and Start/Run/Jog Reverse are both activated, drive will STOP
• If Jog input is activated while the drive is running, the drive will enter Jog mode; when Jog input is deactivated, drive

will STOP

An

fault will occur if the Assertion Level switch (ALsw) position does not match the P120 setting and any

of the digital inputs (P121...P124) are set to a value other than 0.

• An I fault will occur under the following conditions:

- TB-13A...TB-13D settings are duplicated (each setting, except 0 and 3, can only be used once)
- One input is set to “MOP Up” and another is not set to “MOP Down”, or vice-versa.

- One input is set to 10 and another input is set to 11…14.
- One input is set to 11 or 12 and another input is set for 13 or 14.

• Typical control circuits are shown below:

- If any input is set to 10, 12 or 14, P112 must be set to 1 for Reverse action to function.

Run / Stop

with Direction

P121 = 10

Start Forward /

Start Reverse

P121 = 11, P122 = 12

Run Forward /

Run Reverse

P121 = 13, P122 = 14

1

4

13A

FWD

REV

STOP

RUN

1

4

13A 13B

RUN

REV

RUN

FWD

FWD

REV

STOP

1

4 13A 13B

P

Acceleration Time 2

20.0

0.0

{s}

3600

• Selected using TB-13A...TB-13D (P121...

P124 = 17)

• For S-ramp accel/decel, adjust P106

P

Deceleration Time 2

20.0

0.0

{s}

3600

7

Deceleration Time
for Auxiliary Ramp
to Stop

20.0

0.0

{s}

3600

• Selected using TB-13A...TB-13D (P121...

P124 = 19).

• For S-ramp accel/decel, adjust P106
• Once executed, this ramp time has priority

over P105 and P126.

1

Preset Speed #1

0.0

0.0

{Hz}

500

PRESET

SPEED

13A

13B

13C

1

X

--

--

2

--

X

--

3

--

--

X

4

X

X

--

5

X

--

X

6

--

X

X

7

X

X

X

p 2

Preset Speed #2

0.0

0.0

{Hz}

500

p

Preset Speed #3

0.0

0.0

{Hz}

500

p 4

Preset Speed #4

0.0

0.0

{Hz}

500

p

Preset Speed #5

0.0

0.0

{Hz}

500

p

Preset Speed #6

0.0

0.0

{Hz}

500

p 7

Preset Speed #7

0.0

0.0

{Hz}

500

This manual is related to the following products: