Commissioning – Sterling RT User Manual
Page 36

35
SV01H
Commissioning
Code
Possible Settings
IMPORTANT
No.
Name
Default Selection
p 0
PID Setpoint Ramp
20.0
0.0
{s}
100.0
• time of setpoint change from P204 to P205
or vice versa.
• Used to smooth the transition from one PID
setpoint to another, such as when using the
Preset PID Setpoints (P231...P233)
p
Minimum Alarm
0.0
P204
P205
Use with P140, P142 = 18...23
P
Maximum Alarm
0.0
P204
P205
P 1
Preset PID Setpoint
#1
0.0
P204
P205
TB-13A activated; P121 = 3 and
P200 = 1 or 2
P 2
Preset PID Setpoint
#2
0.0
P204
P205
TB-13B activated; P122 = 3 and
P200 = 1 or 2
Preset PID Setpoint
#3
0.0
P204
P205
TB-13C activated; P123 = 3 and
P200 = 1 or 2
P 0
Sleep Threshold
0.0
0.0
{Hz}
500.0
• If drive speed < P240 for longer than P241,
output frequency = 0.0 Hz; drive display =
• P240 = 0.0: Sleep mode is disabled.
• P200 = 0…2: Drive will start again when
speed command is above P240
• P242 > 0.0: Drive will restart when the PID
feedback differs from the setpoint by more
than the value of P242
or when the PID
loop requires a speed above P240.
P 1
Sleep Delay
30.0
0.0
{s}
300.0
P 2
Sleep Bandwidth
0.0
0.0
B
max
Where: B
max
= |(P205 - P204)|