Commissioning – Sterling RT User Manual
Page 26

25
SV01H
Commissioning
Code
Possible Settings
IMPORTANT
No.
Name
Default Selection
P 0
Start Method
0
0 Normal
1 Start on Power-up
Drive will automatically start when power is
applied.
2 Start with DC Brake
When start command is applied, drive will
apply DC braking according to P174, P175
prior to starting the motor
3 Auto Restart
Drive will automatically restart after faults, or
when power is applied.
4 Auto Restart with DC Brake
Combines settings 2 and 3
5 Flying Start/Restart #1
• Drive will automatically restart after faults,
or when power is applied.
• After 3 failed attempts, drive will Auto
Restart with DC brake.
• P110 = 5: Performs speed search, starting
at Max Frequency (P103)
• P110 = 6: Performs speed search, starting
at the last output frequency prior to faulting
or power loss
• If P111 = 0, a flying START is performed
when a start command is applied.
6 Flying Start/Restart #2
NOTE
• P110 = 0, 2: Start command must be applied at least 2 seconds after power-up;
fault will occur if start command is applied too soon.
• P110 = 1, 3…6: For automatic start/restart, the start source must be the terminal
strip and the start command must be present.
• P110 = 2, 4…6: If P175=999.9, dc braking will be applied for 15s.
• P110 = 3…6: Drive will attempt 5 restarts; if all restart attempts fail, drive displays
(fault lockout) and requires manual reset.
• P110 = 5, 6: If drive cannot catch the spinning motor, drive will trip into . fault.
WARNING!
Automatic starting/restarting may cause damage to equipment and/or injury to personnel! Automatic starting/restarting
should only be used on equipment that is inaccessible to personnel.
P 1
Stop Method
0
0 Coast
Drive’s output will shut off immediately upon
a stop command, allowing the motor to coast
to a stop
1 Coast with DC Brake
The drive’s output will shut off and then the DC
Brake will activate (refer to P174, P175)
2 Ramp
The drive will ramp the motor to a stop
according to P105 or P126.
3 Ramp with DC Brake
The drive will ramp the motor to 0 Hz and then
the DC Brake will activate (refer to P174, P175)
Rotation
0
0 Forward Only
If PID mode is enabled, reverse direction is
disabled (except for Jog).
1 Forward and Reverse