Troubleshooting

The connected input/output module is not detected.

Probable Cause

Corrective Action/Description

Reference Page

Module connection or module startup error.

Attached the module while the power was ON.

Turn OFF the power. Detach the input/output module

once and attach it again.

*

The PC software, main module, and input/output

module style and release number rule is not

upheld.

Check the PC software release number and main

module style number before upgrading the version.

[PC software release no.] ≥ [main module style no.] ≥

[input/output module style no.]

**

Carried out an incorrect calibration.

Recalibrate.

4-2

*

See the MW100 Data Acquisition Unit User’s Manual (IM MW100-01E).

**

See the MW100 Data Acquisition Unit Operation Guide (IM MW100-01E).

5.1 Troubleshooting