beautypg.com

Yokogawa Data Acquisition with PID Control CX2000 User Manual

Page 9

background image

1-3

IM 04L31A01-01E

Principles of Operation

1

Calculation Function

The CX1000/CX2000 performs differential computation, linear scaling, and square roots

using a microprocessor on the CPU board.

Measurement Alarm Function

The following eight alarm types can be set.

High limit (H), low limit (L), differential high limit (h), differential low limit (l), rate-of-

change on increase (R), rate-of-change on decrease (r), alarm delay upper limit alarm

(T), or alarm delay lower limit alarm (t).

Control Alarm Function

The following nine alarm types can be set.

PV high-limit, PV low-limit, Deviation high-limit, Deviation low-limit, Deviation high & low

limit, SP high-limit, SP low-limit, Output high-limit, Output low-limit

Other Functions

• Communication Function:

Ethernet (standard)

RS-232/RS-422A interface added (optional).

• Remote Function:

The trigger, start/stop, time adjustment, and other functions can be controlled

remotely (optional).

• Measurement Alarm Relay:

Measurement alarm output and memory end/fail output (option for CX1006 and

CX2000).

• Transmitter Power Supply:

DC24 V output for transmitter (only CX2000’s optional).

• VGA Out Function (Option for CX2000 Only):

The instrument's screen can be displayed on an external monitor via VGA output.

• Control - Purpose DIO (CX2000 Only):

Contact input

Input for designated operations such as start/stop. Activate using a no-voltage

contact or open collector signal. This is a 12-point input.

Contact output

Control Alarm output consists of 12 points of transistor contact output.

Control Output Section

Control Output

The following types are available for universal control output.

• Current output (continuous PID control output)

Continuously output a current (analog signal) proportional to the calculated PID values.

• Time proportional PID voltage pulse output

Output an ON/OFF signal, having a pulse width proportional to the time, as a voltage

per the calculated PID values.

• On/Off control relay contact output

• Output an ON/OFF signal, having a pulse width proportional to the time, at a relay

contact point per the calculated PID values.

• Output an ON/OFF signal to a relay contact point corresponding to the sign (+/–) of

the deviation in the measured value from the specified target value.

Contact Input

Input for designated operations such as start/stop. Activate using a no-voltage contact

or open collector signal.

Contact Output

Control Alarm output consists of relay contact output and transistor contact output.

1.2 Input Section