2-7

SM 04L31A01-01E

Testing

2

Current Output Accuracy

1.

Change the mode to setup and choose Control, Control action, and then Input

setting. Set the control mode to Single. Press the ESC key to return to the

preceding menu, and choose Output processing.

2.

Set the type of control output to Current-output and analog output to 4-20 mA

for all the loops, save the settings, and change the mode to normal (the cycle

time can be set freely).

3.

Press the DISP/ENTER key and choose Control and then Control groups to

display the control display.

4.

Choose a loop number to measure with a blue arrow using the arrow keys.

5.

Press the MODE softkey, and change the operation mode to manual by

choosing MAN with the up and down arrow keys and pressing DISP/ENTER key

to confirm it.

6.

Press the RUN/STP softkey, and start control operation by choosing RUN with

the up and down arrow keys and pressing DISP/ENTER key to confirm it.

7.

Press the OUT softkey. Set the output ratio to 0.0% and 100.0% with the up and

down arrow keys and measure each output current with an ammeter or the like.

Verify that the measured currents are within the ranges as shown in the table

below.

Output Ratio

Reference Value

Allowable Range

0.0%

4 mA

3.984 to 4.016 mA

100.0%

20 mA

19.984 to 20.016 mA

(Load condition: 250

±1%)

Voltage Pulse Output

1.

Choose Output processing by following the procedures in step 1 of “Current

Output Accuracy.”

2.

Set the type of control output to Voltage-pulse and the cycle time to 1 second

for all the loops, save the settings, and change the mode to normal (the type of

analog output can be set freely).

3.

Change the operation mode to manual and start control operation by following

the procedures of steps 5 and 6 of “Current Output Accuracy.”

4.

Press the OUT softkey. Set the output ratio to 20.0% with the up and down

arrow keys and observe the output voltage waveform on an oscilloscope or the

like. Verify that a rectangular waveform is displayed at a 1-second interval (0.2-

second high and 0.8-second low) and 12 V

±

5%.

Control Relay Output

1.

Choose Output processing by following the procedures in step 1 of “Current

Output Accuracy.”

2.

Set the type of control output to On/Off-control for all the loops, save the

settings, and change the mode to normal (the cycle time and type of analog

output can be set freely).

3.

Change the operation mode to manual and start control operation by following

the procedures of steps 5 and 6 of “Current Output Accuracy.”

4.

Press the OUT softkey. Set the output ratio to 0.0% and 100.0% with the up and

down arrow keys and verify that the relay outputs are as follows:

Output Ratio

NO-C

NC-C

0.0% Break Make

100.0% Make Break

2.2 Test Procedures