2.10.13 General Communication Log (FLog)
The output in response to the command “FLog,General” is shown below.
Syntax
EA
yyyy/mo/dd_hh:mm:ss_nn_uuu…u_fdmmm…m
…
EN
yyyy/mo/dd_hh:mm:ss Time of command Tx/Rx
yyyy
Year (1900 to 2099)
mo
Month (01 to 12)
dd
Day (01 to 31)
hh
Hour (00 to 23)
mm
Minute (00 to 59)
ss
Second (00 to 59)
nn
Connection ID
s0
Serial (general)
e0
Ethernet connection #0 (general)
e1
Ethernet connection #1 (general)
e2
Ethernet connection #2 (general)
uuu…u
User name (fixed to 20 characters. Unused character positions
are filled with spaces.)
f
Multiple command flag
Space
Single command
*
Multiple commands
d
Tx/Rx
>
Tx (command: connected instrument to
GX/GP)
<
Rx (Response: GX/GP to connected
instrument)
mmm…m
Message (fixed to 40 characters. Unused character positions are
filled with spaces.)
The GX/GP normally outputs the data that has been transmitted
or received as-is, but it sometimes outputs special messages.
Special messages are shown below.
(output)
Data output
(Over length)
Command length too long
(timed out)
Timeout
(disconnected)
Disconnection (occurs when an
Ethernet connection is disconnected)
2.10 ASCII Output Format