12 app, Srangeai measurement range of ai channel – Yokogawa Touch Screen GP20 User Manual
Page 27
2-13
IM 04L51B01-17EN
Commands and Responses
1
2
App
SRangeAI
Measurement Range of AI Channel
Sets the measurement range of an AI channel.
Unused Channels
Syntax SRangeAI,p1,p2
p1 Channel number
p2 Input type (Skip)
Channels Whose Input Type Is DI and No Math
Syntax SRangeAI,p1,p2,p3,p4,p5,p6
p1 Channel number
p2 Input type (DI)
p3 Range (see “Description.”)
P4 Calculation type (Off)
p5 Span lower limit
p6 Span upper limit
Channels Whose Input Type Is Volt, TC, or RTD and
No Calculation
Syntax SRangeAI,p1,p2,p3,p4,p5,p6,p7
p1 Channel number
p2 Input type (Volt, TC, RTD)
p3 Range (see “Description.”)
P4 Calculation type (Off)
p5 Span lower limit
p6 Span upper limit
p7 Bias (–999999 to 999999)
Delta Channels
Syntax SRangeAI,p1,p2,p3,p4,p5,p6,p7,p8
p1 Channel number
p2 Input type (Volt, TC, RTD, DI)
p3 Range (see “Description.”)
P4 Calculation type (Delta)
p5 Span lower limit
p6 Span upper limit
p7 Bias (–999999 to 999999) (can be set
when p2 is not set to DI)
p8 Reference channel number
Scaling Channels
Syntax SRangeAI,p1,p2,p3,p4,p5,p6,p7,p8,p
9,p10,p11
p1 Channel number
p2 Input type (Volt, TC, RTD, DI)
p3 Range (see “Description.”)
P4 Calculation type (Scale)
p5 Span lower limit
p6 Span upper limit
p7 Bias (–999999 to 999999) (can be set
when p2 is not set to DI)
p8 Decimal Place (0 to 5)
p9 Scaling lower limit
p10 Scaling upper limit
p11 Unit (up to 6 characters, UTF-8)
Unified Signal Input Channels (Input Type Is GS)
Syntax SRangeAI,p1,p2,p3,p4,p5,p6,p7,p8,p
9,p10,p11,p12,p13
p1 Channel number
p2 Input type (GS)
p3 Range (see “Description.”)
P4 Calculation type (Scale)
p5 Span lower limit
p6 Span upper limit
p7 Bias (–999999 to 999999)
p8 Decimal Place (0 to 5)
p9 Scaling lower limit
p10 Scaling upper limit
p11 Unit (up to 6 characters, UTF-8)
p12 Low-cut function (Off, On)
p13 Low-cut output (Zero, Linear)
Square Root Channels
Syntax SRangeAI,p1,p2,p3,p4,p5,p6,p7,p8,p
9,p10,p11,p12,p13,p14
p1 Channel number
p2 Input type (Volt, GS)
p3 Range (see “Description.”)
P4 Calculation type (Sqrt)
p5 Span lower limit
p6 Span upper limit
p7 Bias (–999999 to 999999)
p8 Decimal Place (0 to 5)
p9 Scaling lower limit
p10 Scaling upper limit
p11 Unit (up to 6 characters, UTF-8)
p12 Low-cut function (Off, On)
p13 Low-cut output (Zero, Linear)
p14 Low-cut point (0 to 50)
Query
SRangeAI[,p1]?
Example Measure -0.5000 to 1.0000 V on channel 0002.
No scaling. No bias.
SRangeAI,0002,Volt,2V,Off,–5000,
10000,0
Description
• You cannot use this command to configure settings
while recording is in progress.
• You cannot use this command to configure settings
while computation is in progress.
• If p2=TC/RTD/DI, you cannot specify p4=Sqrt.
• If p2=GS, you cannot specify p4=Off/Delta.
• If p2=DI, you cannot set p7.
• RTD cannot be specified if an electromagnetic relay
scanner type (Type suffix code: -T1) analog input
module is in use.
• The settable items for p3 are shown below.
2.4 Setting Commands