Sbarmath bar graph display (/mt), Spartialmath partial expanded display (/mt), Sbandmath color scale band (/mt) – Yokogawa Touch Screen GP20 User Manual
Page 36: Salmmarkmath alarm mark (/mt)

2-22
IM 04L51B01-17EN
Query
SScaleMath[,p1]?
Example Display the math channel 015 scale at display
position 1. Display four equally spaced main
scale marks.
SScaleMath,015,1,4
SBarMath
Bar Graph Display (/MT)
Sets the bar graph display of a math channel.
Syntax SBarMath,p1,p2,p3
p1 Channel number
p2 Bar display base position
Lower Lower
Center Center
Upper Upper
p3 Number of scale divisions (4 to 12)
Query
SBarMath[,p1]?
Example Display the computed values of math channel
015 on a bar graph with the center set as the
base position (Center). Display four equally
spaced main scale marks.
SBarMath,015,Center,4
SPartialMath
Partial Expanded Display (/MT)
Sets the partial expanded display of a math channel
waveform.
Syntax SPartialMath,p1,p2,p3,p4
p1 Channel number
p2 Partial expanded On/Off (On, Off)
p3 Partial expanded boundary position [%] (1
to 99)
P4 Partial expanded boundary value
Query
SPartialMath[,p1]?
Example For channel 015 whose measurement range is
0 to 1.0000 V, display the measured value of
0.7500 V at the 50% position.
SPartialMath,015,On,50,7500
Description
• You cannot set this on a “Off” channel. p2 is fixed to
Off.
• If p2=Off, you cannot set p3 or subsequent
parameters.
• P2=On can be specified when the difference between
the span upper and lower limits is 2 digits or greater.
SBandMath
Color Scale Band (/MT)
Sets the color scale band of a math channel.
Syntax SBandMath,p1,p2,p3,p4,p5,p6,p7
p1 Channel number
p2 Color scale band (Off, In, Out)
p3 R value of the color scale band RGB
colors (0 to 255)
P4 G value of the color scale band RGB
colors (0 to 255)
p5 B value of the color scale band RGB
colors (0 to 255)
p6 Upper limit of the color scale band display
(span lower limit to span upper limit)
p7 Lower limit of the color scale band display
(span lower limit to span upper limit)
Query
SBandMath[,p1]?
Example For math channel 015, set a blue band in the
range of -0.5000 to 1.0000.
SBandMath,015,In,0,0,255,5000,
10000
Description
• You cannot set this on a “Off” channel. p2 is fixed to
Off.
• If p2=Off, you cannot set p3 or subsequent
parameters.
• For details on RGB values, see “Description” of the
SAlmMarkMath
Alarm Mark (/MT)
Sets the display of the marker that indicates the specified
alarm position of a math channel.
Syntax SAlmMarkMath,p1,p2,p3,p4,p5,p6,p7,
p8,p9,p10,p11,p12,p13,p14,p15
p1 Channel number
p2 Whether to display the alarm mark on the
scale (Off, On)
p3 Alarm mark type
Alarm Display the default alarm mark
Fixed Display the mark with the
specified color
P4 R value of the RGB mark colors for alarm
1 ( 0 to 255)
p5 G value of the RGB mark colors for alarm
1 ( 0 to 255)
p6 B value of the RGB mark colors for alarm
1 ( 0 to 255)
p7 R value of the RGB mark colors for alarm
2 ( 0 to 255)
p8 G value of the RGB mark colors for alarm
2 ( 0 to 255)
p9 B value of the RGB mark colors for alarm
2 ( 0 to 255)
p10 R value of the RGB mark colors for alarm
3 ( 0 to 255)
p11 G value of the RGB mark colors for alarm
3 ( 0 to 255)
p12 B value of the RGB mark colors for alarm
3 ( 0 to 255)
p13 R value of the RGB mark colors for alarm
4 ( 0 to 255)
p14 G value of the RGB mark colors for alarm
4 ( 0 to 255)
p15 B value of the RGB mark colors for alarm
4 ( 0 to 255)
Query
SAlmMarkMath[,p1]?
Example Display the alarm marks for alarms 1 to 4 of
math channel 015 in fixed colors red, brown,
orange, and yellow, respectively.
2.4 Setting Commands