2 most recent (do channel) status (frelay), 2 most recent (do channel) status (frelay) -58, For the output format, see – Yokogawa Touch Screen GP20 User Manual
Page 72

2-58
IM 04L51B01-17EN
V_¯_¯_¯_¯_ V
^C_¯_¯_¯_¯ °C
f
Sign (+ or -)
dddddddd
Mantissa (00000000 to 99999999; 8 digits)
For erroneous data (data status is E), the mantissa is 99999999.
If the data status is O (±over), the mantissa is 99999999 (+over) or
–99999999 (–over).
If the data status is B (burnout), the mantissa is 99999999 (+burnout) or
–99999999 (–burnout).
pp
Exponent (00 to 05)
2.10.2 Most Recent (DO Channel) Status (FRelay)
The output in response to the command “FRelay,0” is shown below.
Syntax
EA
M00:aaa…
M01:aaa…
M02:aaa…
M03:aaa…
M04:aaa…
M05:aaa…
M06:aaa…
M07:aaa…
M08:aaa…
M09:aaa…
EN
aaa…
Outputs the relay (DO channel) status of module numbers 00 to 09.
If the module installed in the corresponding module number is not a DO module,
a hyphen is output.
If the module installed in the corresponding module number is a DO module, “1”
or “0” is output for the number of channels in the module in ascending order by
channel number.
“1” indicates relay (DO channel) ON state, and “0” indicates relay (DO channel)
OFF state.
2.10 ASCII Output Format