Sreport report type (/mt), Srepdata report data (/mt) – Yokogawa Touch Screen GP20 User Manual
Page 42
2-28
IM 04L51B01-17EN
p3
P4
p5
p6
Event Type
Value
Source
Element
Number
Alarm
Level
Operation
mode
Internal Switch
SW
1 to 100
-
Rising, Falling,
Both
Remote control input DI
Channel
number
-
Rising, Falling,
Both
Relay (DO channel) DO
Channel
number
-
Rising, Falling,
Both
Alarm
(I/O channel)
AlarmIO
Channel
number
1 to 4
Rising, Falling,
Both
Alarm
(math channel)
AlarmMath
Channel
number
1 to 4
Rising, Falling,
Both
Alarm
(communication
channel)
AlarmCom
Channel
number
1 to 4
Rising, Falling,
Both
Alarm
AlarmAll
-
-
Rising, Falling,
Both
Timer
Timer
1 to 4
-
Edge
Match time timer
MatchTimeTimer 1 to 4
-
Edge
Conditions p7
p8
p9
p10
p6
Action Type
Value
Source
Element
Number
Action
Detail 1
Action
Detail 2
Rising,
Falling,
Edge
Recording
Memory
-
Start, Stop -
Math (math channel) Math
-
Start,
Stop,
Reset
-
Display rate switch
RateChange
1, 2
-
-
Flag
Flag
1 to 20
-
-
Manual sample
ManualSample
-
-
-
Alarm ACK
AlarmACK
-
-
-
Snapshot
Snapshot
-
-
-
Time adjustment
TimeAdjust
-
-
-
Display data save
SaveDisplay
-
-
-
Event data save
SaveEvent
1
-
-
Event trigger
Trigger
1
-
-
Message
Message
1 to 100 All, Select 1 to 50
Display group
change
GroupChange
1 to 50
-
-
Relative timer reset TimerReset
1 to 4
-
-
Settings load
ConfigLoad
1 to 3
-
-
Favorite screen
display
PlayList
1 to 20
-
-
Both
Recording start/stop MemoryStartStop -
-
-
Math start/stop
MathStartStop
-
-
-
Display rate switch
1/2
RateChange1_2 -
-
-
Flag On/Off
FlagOn_Off
1 to 20
-
-
Query
SEventAct[,p1]?
Invalid parameters are returned as blanks in
queries.
Example Execute memory start on the rising edge of the
remote control input (channel 0101). Use event
action number 2.
SEventAct,2,On,DI,0101,,Rising,Mem
ory,,Start
Description
• There are limitations to event and action
combinations. For details, see section 1.14 in the
Models GX10/GX20/GP10/GP20 Paperless Recorder
User’s Manual (IM 04L51B01-01EN).
• Write only delimiters (commas) for irrelevant
parameters (invalid even if a value is specified).
• Event type “DI” is the channel of the DI module that
has been set to remote module (
• Math channel and flag are an option (/MT).
• Communication channels are an option (/MC).
SReport
Report Type (/MT)
Sets the type of report to create.
No Reports
Syntax SReport,p1
p1 Type (Off)
Hourly and Daily Reports
Syntax SReport,p1,p2
p1 Type (Hour+Day)
p2 Time to create reports: Hour (HH) (00 to
23)
Daily and Weekly Reports
Syntax SReport,p1,p2,p3
p1 Type (Day+Week)
p2 Day to create reports (Mon, Tue, Wed, Thu,
Fri, Sat, Sun)
p3 Time to create reports: Hour (HH) (00 to
23)
Daily and Monthly Reports
Syntax SReport,p1,p2,p3
p1 Type (Day+Month)
p2 Day to create reports (1 to 28)
p3 Time to create reports: Hour (HH) (00 to
23)
Batch Reports
Syntax SReport,p1,p2
p1 Type (Batch)
p2 Recording interval (10min, 15min, 30min,
1h)
Day Custom Reports
Syntax SReport,p1,p2,p3,p4,p5
p1 Type (Custom)
p2 Recording interval (10min, 15min, 30min,
1h)
p3 File creation interval (4h, 6h, 8h, 12h, 24h)
P4 Time to create reports: Hour (HH) (00 to
23)
p5 Time to create reports: Minute (MM) (00
to 59)
Query
SReport[,p1]?
Example Create daily reports at 09:00 every day and
monthly reports at 09:00 on the first day of
each month.
SReport,Day+Month,1,09
Description
• You cannot use this command to configure settings
while recording is in progress.
• You cannot use this command to configure settings
while computation is in progress.
• If p1=Off, you cannot set p2 or subsequent
parameters.
SRepData
Report Data (/MT)
Sets the data type and file type of reports.
Syntax SRepData,p1,p2,p3,p4,p5,p6
p1 Data type 1 (Max, Min, Ave, Sum, Inst)
p2 Data type 2 (Off, Max, Min, Ave, Sum,
Inst)
p3 Data type 3 (Off, Max, Min, Ave, Sum,
Inst)
2.4 Setting Commands