2-1

IM 04L51B01-17EN

Commands and Responses

1

2

App

2.1 Command Transmission and GX/GP Responses

2.1.1

General Communication

The GX/GP can work with various applications through the use of commands.

The communication that is achieved through commands is referred to as “general

communication.”

2.1.2

Command Types and Functions

The following types of commands are available. The first character of command names

represents the command type. For example, in the command “SRangeAI,” “S” represents

the command type. The second and subsequent characters represent the contents of

commands.

Type

Description

Operation commands
Example:

OSetTime

Commands that start with “O.” These commands are used

to operate the GX/GP.

Setting commands
Example:

SRangeAI

Commands that start with “S.” These commands change

the GX/GP settings.

Output commands
Example:

FData

Commands that start with “F.” These commands cause the

GX/GP to output measured data and other types of data.

Communication Control commands
Example:

CCheckSum

Commands that start with “C.” These commands control the

communication with the GX/GP.

Instrument information output

commands
Example:

_MFG

Commands that start with an underscore. These commands

cause the GX/GP to output its instrument information.

2.1.3

Command Syntax

A Single Command

A single command consists of a command name, parameters, delimiters, and terminator.

The command name is written in the beginning, and parameters follow. Delimiters are used

to separate the command name from parameters and between each parameter. A delimiter

is a symbol that indicates a separation. A terminator is attached to the end of a command.

Delimiters

Command name,parameter 1,parameter 2 terminator

Example of a Command

SRangeAI,0001,VOLT,2V,OFF,-15000,18000,0

Commands in a Series (Setting commands only)

You can send multiple setting commands in a series. When writing a series of commands,

separate each command with a sub delimiter. A sub delimiter is a symbol that indicates a

separation. A terminator is attached to the end of the series. The maximum number of bytes

that can be sent at once is 8000 bytes (8000 characters).

Sub delimiter

Command name,parameter 1,parameter 2;command name,parameter1 terminator

(Command 1)

(Command 2)

Chapter 2 Commands and Responses