Srangedi measurement range of di channel, Srangedo do channel operation – Yokogawa Touch Screen GP20 User Manual
Page 28
2-14
IM 04L51B01-17EN
p2=Volt p2=TC
p2=RTD
p2=GS
p2=DI
20mV
R
Pt100
1-5V
Level
60mV
S
Pt100-H
0.4-2V
DI
200mV B
JPt100
1V
K
JPt100-H
2V
K-H
Cu10GE
6V
E
Cu10LN
20V
J
Cu10WEED
50V
T
Cu10BAILEY
N
Cu10a392
W
Cu10a393
L
Cu25
U
Cu53
PLATINEL
Cu100
PR20-40
J263B
WRe3-25
Ni100SAMA
KpvsAu7Fe Ni100DIN
NiNiMo
Ni120
WWRe26
Pt25
N14
Pt50
XK
Pt200WEED
Cu10G
Cu50G
Cu100G
Pt46G
Pt100G
SRangeDI
Measurement Range of DI Channel
Sets the measurement range of a DI channel.
Unused Channels
Syntax SRangeDI,p1,p2
p1 Channel number
p2 Input type (Skip)
Channels That Are Not Delta or Scaling
Syntax SRangeDI,p1,p2,p3,p4,p5,p6
p1 Channel number
p2 Input type (DI)
p3 Fixed at “-.”
P4 Calculation type (Off)
p5 Span lower limit (0 to 1)
p6 Span upper limit (0 to 1)
Delta Channels
Syntax SRangeDI,p1,p2,p3,p4,p5,p6,p7
p1 Channel number
p2 Input type (DI)
p3 Fixed at “-.”
P4 Calculation type (Delta)
p5 Span lower limit (0 to 1)
p6 Span upper limit (0 to 1)
p7 Reference channel number
Scaling Channels
Syntax SRangeDI,p1,p2,p3,p4,p5,p6,p7,p8,p
9,p10
p1 Channel number
p2 Input type (DI)
p3 Fixed at “-.”
P4 Calculation type (Scale)
p5 Span lower limit (0 to 1)
p6 Span upper limit (0 to 1)
p7 Decimal Place (0 to 5)
p8 Scaling lower limit
p9 Scaling upper limit
p10 Unit (up to 6 characters, UTF-8)
Query
SRangeDI[,p1]?
Example Measure 0 to 1 on channel 0103. No scaling.
SRangeDI,0103,DI,-,Off,0,1
Description
• You cannot use this command to configure settings
while recording is in progress.
• You cannot use this command to configure settings
while computation is in progress.
SRangeDO
DO Channel Operation
Sets the DO channel operation.
Alarm Output
Syntax SRangeDO,p1,p2,p3,p4,p5,p6,p7,p8
,p9
p1 Channel number
p2 Output type (Alarm)
p3 Span lower limit (0 to 1)
P4 Span upper limit (0 to 1)
p5 Unit (up to 6 characters, UTF-8)
p6 Energize or de-energize
Energize
Energize the relay (DO
channel) during output.
De_energize De-energize the relay
(DO channel) during
output.
p7 Operation
And
Operate when all set alarms are
in the alarm state.
Or
Operate when any of the set
alarms are in the alarm state.
p8 Hold or nonhold
Hold
Hold output until an
alarm ACK operation.
Nonhold
Clear output when the
alarm is cleared.
p9 Relay (DO channel) action on
acknowledge (Normal, Reset)
Alarm Output (Reflash)
Syntax SRangeDO,p1,p2,p3,p4,p5,p6,p7,p8
,p9
p1 Channel number
p2 Output type (Alarm)
p3 Span lower limit (0 to 1)
P4 Span upper limit (0 to 1)
p5 Unit (up to 6 characters, UTF-8)
p6 Energize or de-energize
Energize
Energize the relay (DO
channel) during output.
De_energize De-energize the relay
(DO channel) during
output.
p7 Action (Reflash)
p8 Reflash time (500ms, 1s, 2s)
2.4 Setting Commands