12 app, Four-wire system, Two-wire system – Yokogawa Touch Screen GP20 User Manual
Page 13
1-7
IM 04L51B01-17EN
Using Dedicated Commands (General)
1
2
App
• Four-wire system
Generally, a four-wire system is used to connect to a host device. In the case of a four-
wire system, the transmission and reception lines need to be crossed over.
Terminator (external) 120 Ω 1/2W or greater
#1
Do not connect terminators to #1 through #n-1.
RS-422/485
terminal on the GX/GP
#2
#n
(#n 32)
Terminator (external)
Host device
side
SG
RDB( + )
RDA( – )
SDB( + )
SDA( – )
FG
SG
RDB+
RDA–
SDB+
SDA–
(SG)
(RDB
+
)
(RDA
–
)
(SDB
+
)
(SDA
–
)
FG
SG
RDB+
RDA–
SDB+
SDA–
(SG)
(RDB
+
)
(RDA
–
)
(SDB
+
)
(SDA
–
)
FG
SG
RDB+
RDA–
SDB+
SDA–
(SG)
(RDB
+
)
(RDA
–
)
(SDB
+
)
(SDA
–
)
• Two-wire system
Connect the transmission and reception signals with the same polarity on the RS-422/485
terminal block. Only two wires are used to connect to the external device.
Terminator (external) 120 Ω 1/2W or greater
#1
Do not connect terminators to #1 through #n-1.
RS-422/485
terminal on the GX/GP
#2
#n
(#n 31)
Terminator (external)
Host device
SG
RDB( + )
RDA( – )
SDB( + )
SDA( – )
FG
SG
RDB+
RDA–
SDB+
SDA–
(SG)
(B+)
(A
–
)
(B+)
(A
–
)
FG
SG
RDB+
RDA–
SDB+
SDA–
(SG)
FG
SG
RDB+
RDA–
SDB+
SDA–
(SG)
(B+)
(A
–
)
Note
• The method used to eliminate noise varies depending on the situation. In the connection
example, the shield of the cable is connected only to the GX/GP’s ground (one-sided
grounding). This is effective when there is a difference in the electric potential between
the computer’s ground and the GX/GP’s ground. This may be the case for long distance
communications. If there is no difference in the electric potential between the computer’s ground
and the GX/GP’s ground, the method of connecting the shield also to the computer’s ground
may be effective (two-sided grounding). In addition, in some cases, using two-sided grounding
with a capacitor connected in series on one side is effective. Consider these possibilities to
eliminate noise.
• When using the two-wire interface (Modbus protocol), the 485 driver must be set to high
impedance within 3.5 characters after the last data byte is sent by the host computer.