3 data output response, Data output response -54, Ascii output – Yokogawa Touch Screen GP20 User Manual
Page 68

2-54
IM 04L51B01-17EN
Response Example 3
In a string of two commands, if error number 10 occurs in the second parameter of the first
command and error number 500 occurs in the fifth parameter of the second command, the
GX/GP outputs:
E1,10:1:2,500:2:5
Error Messages
You can use the “instrument’s error number information output command” (_ERR) to output
the error message that corresponds to an error number of a negative response.
2.9.3
Data Output Response
There are two types of data output: ASCII and binary.
ASCII Output
The responses to the following commands are in ASCII.
• Queries for operation commands and setting commands
• ASCII data output requests of output commands
Syntax
EACRLF
ASCII string data
• • • • • • • • CRLF
ASCII string data
• • • • • • • • CRLF
|
ASCII string data
• • • • • • • • CRLF
ENCRLF
The GX/GP adds a header (EA) in front of the ASCII string output data and a footer (EN)
at the end. The GX/GP adds the two characters CRLF to the end of headers, footers, and
ASCII string data.
2.9 Responses to Commands