beautypg.com

12 app, Strdline trend line width, grid, Strdrate trend interval switching – Yokogawa Touch Screen GP20 User Manual

Page 45: Strdkind trend type, Strdpartial partial expanded trend display, Smsgbasic message writing, Sgroup display group

background image

2-31

IM 04L51B01-17EN

Commands and Responses

1

2

App

Example Set the number of digits to display for scale

values to “Fine,” display the value indicators

on a bar graph, and set the number of digits

to display for channels that are added to the

current value mark to 4 digits.

StrdScale,Fine,Bar,4-digit

STrdLine

Trend Line Width, Grid

Sets the trend waveform line width and the grid in the

display area.

Syntax STrdLine,p1,p2

p1 Line width

Thick

Thick

Normal

Normal

Thin

Thin

p2 Grid

Auto

Auto

4 to 12

Number of grid lines

Query

STrdLine?

Example Set the trend waveform line width to “Thin” and

the number of grid lines to 10.

StrdLine,Thin,10

STrdRate

Trend Interval Switching

Sets the trend interval switching.

Syntax STrdRate,p1,p2

p1 Trend interval switching

Off

Not switch

On

Switch

p2 Second trend interval (5s, 10s, 15s, 30s,

1min, 2min, 5min, 10min, 15min, 20min,

30min, 1h, 2h, 4h, 10h).

Query

STrdRate?

Example Set the second trend interval to 30 seconds.

STrdRate,On,30s

Description
You cannot set parameter p1 while recording is in

progress.

You cannot set parameter p1 while computation is in

progress.

p2 is valid only when p1=On.
You cannot choose a second trend interval that is

shorter than the scan interval.

Trend intervals shorter than 30 s cannot be specified

if an electromagnetic relay scanner type (Type suffix

code: -T1) analog input module is in use (set up).

STrdKind

Trend Type

Sets the type of trend waveform to display.

Syntax STrdKind,p1

p1 Type

Fixed to "T-Y"

Query

STrdKind?

Example Display using rectangular coordinates.

STrdKind,T-Y

STrdPartial

Partial Expanded Trend Display

Enable or disable the partial expanded trend display.

Syntax STrdPartial,p1

p1 Disable or enable (Off, On)

Query

STrdPartial?

Example Enable the partial expanded trend display.

STrdPartial,On

SMsgBasic

Message Writing

Sets the message writing operation.

Syntax SMsgBasic,p1,p2,p3

p1 Message writing method

Common

Write messages to all display

groups.

Separate Write messages to only the

groups that are displayed.

p2 Power failure message (Off, On)

p3 Change message (Off, On)

Query

SMsgBasic?

Example Write messages to only the groups that are

displayed. Enable the power failure message

and change message.

SMsgBasic,Separate,On,On

SGroup

Display Group

Sets the display group.

Syntax SGroup,p1,p2,p3,p4

p1 Group number

p2 Enable or disable (Off, On)

p3 Group name (up to 16 characters, UTF-8)

P4 Channel string

Specify using channel numbers. 4-digit

numbers for I/O channels. Numbers

that start with “A” for math channels

(A015). Numbers that start with “C” for

communication channels (C020). The

maximum number of characters per

channel is 4.

Use periods to separate channel

numbers (see example).

Query

SGroup[,p1]?

The channel string is output exactly as it is

specified.

2.4 Setting Commands