7 gx status (fstat), 7 gx status (fstat) -63, Ascii output format, see – Yokogawa Touch Screen GP20 User Manual
Page 77: 12 app
2-63
IM 04L51B01-17EN
Commands and Responses
1
2
App
2.10.7 GX status (FStat)
The output in response to the command “FStat,0” is shown below.
Syntax
EA
aaa.bbb.ccc.ddd
EN
aaa
Status information 1 (see table below)
bbb
Status information 2 (see table below)
ccc
Status information 3 (see table below)
ddd
Status information 4 (see table below)
Status Information 1
Bit
Name
Description
0
-
-
1
Memory sampling
Set to 1 during recording
2
Computing
Set to 1 while computation is in progress.
3
Alarm activated
Set to 1 when an alarm is activated.
4
Accessing medium
Set to 1 while the SD medium is being accessed.
5
E-mail started
Set to 1 while the e-mail transmission has been started.
6
Buzzer activated
Set to 1 when the buzzer is activated.
7
-
-
Status Information 2
Bit
Name
Description
0
-
-
1
-
-
2
Memory end
Set to 1 when the free space in the external memory is low.
3
Touch operation
login
Set to 1 when a user is logged in through touch operation.
4
-
-
5
-
-
6
Measurement
error
Set to 1 while measurement errors are detected on an AI
module or when a burnout has occurred.
7
Communication
error
Set to 1 when there is any command that is blocking Modbus
master or Modbus client communication.
Status 3 and 4 are edge operations. They are cleared when read.
Status Information 3
Bit
Name
Description
0
Computation dropout
Set to 1 when computation cannot keep up.
1
Decimal and unit
information setting
Set to 1 when the decimal or unit information is
changed.
2
Command error
Set to 1 when there is a command syntax error.
3
Execution error
Set to 1 when there is a command execution error.
4
SNTP error at startup
Set to 1 when SNTP time synchronization fails at
startup.
5
-
-
6
-
-
7
-
-
2.10 ASCII Output Format