Yokogawa AXFA14G/C User Manual
Page 35
IM 01E20C02-01E
6-6
6. PARAMETER DESCRIPTION
(5) Item E (Menu E): Pulse Setting items
Menu E contains items relevant to pulse output. This is used to set parameters such as the pulse scale and width.
T0606.EPS
Item
Name
Display unit
(BRAIN)
Data range
Display unit
/BRAIN
Default value
(*): Indicated item
Units
R/W
Position
of decimal
point
Description
Pulse Unit
(PULSE UNIT)
50% Duty
Pulse Set
(PULSE SET)
Pulse Width
(PULSE WIDTH)
0
3 %
%
W
Pulse Low Cut
(PULSE LOWCUT)
Pulse Scale
(PULSE SCALE)
E10
(B32)
W
n Unit/P
u Unit/P
m Unit/P
Unit/P
k Unit/P
M Unit/P
Pulse/s
0 to 32000
W
0 to 4
W
50% Duty
0.05 ms
0.1ms
0.5 ms
1 ms
20 ms
33 ms
50 ms
100 ms
0 to 100
R
Good
Error
—
(SELF CHECK)
E12
E60
E13
See “6.5 Alarm Function”.
Selects the pulse width for pulse
output.
Sets the flow rate per one pulse
as used for pulse output. Linked
with B33.
Sets the range in vicinity of 0%
within which pulse output will be
halted.
E11
E10
0 (*)
Selects the flow rate unit per one
pulse as used for pulse output.
Linked with B32.
Pulse/s (*)
E00
(6) Item F (Menu F): Status Functions Setting items
Menu F contains items relevant to multiplex range output and other status Input/Output.
T0607-1.EPS
Item
Name
Display unit
(BRAIN)
Data range
Display unit
/BRAIN
Default value
(*): Indicated item
Units
R/W
Position
of decimal
point
Description
No Function
Pulse Output
Alarm Output
Warning Output
Total Switch (O)
H/L Alarm (O)
HH/LL Alarm (O)
Fwd/Rev Rngs (O)
Auto 2 Rngs (O)
Auto 3 Rngs (O)
Auto 4 Rngs (O)
Ext 2 Answer (O)
Pulse Output
W
DO Function
(DO FUNCTION)
Status Function
(STATUS FUNC)
No Function
DIO Function
(DIO FUNCTION)
No Function
Alarm Output
Warning Output
Total Switch (O)
H/L Alarm (O)
HH/LL Alarm (O)
Fwd/Rev Rngs (O)
Auto 2 Rngs (O)
Auto 3 Rngs (O)
Auto 4 Rngs (O)
Ext 2 Answer (O)
0% Singal Lock (I)
Ext Auto Zero (I)
Ext Ttl Set (I)
Ext R Ttl Set (I)
Ext 2 Ttl Set (I)
Selects function for the DO
terminal
Selects function for the DIO
terminal
W
F21
F20
F00