10. MAINTENANCE

10.3 Troubleshooting

Although magnetic flowmeters rarely require maintenance, failures may occur when the
instrument is not operated correctly. This section describes troubleshooting procedures
where the cause of the breakdown is identified through receiver indication.

10.3.1 No Indication

Is an error being displayed? Check the converter display.

NO

YES

NO

NO

YES

NO

YES

NO

Is an error being

displayed?

Is anything else

being displayed?

YES

YES

Check whether the flowtube
is filled with fluid.

Is the flowtube

full of fluid?

Remove the tube and
inspect the inside of the pipe.

Is foreign

matter adhering to

the walls?

Does the

arrow on the tube match the

flow direction?

Examine in accordance with
Section 6.5: Alarms.

Perform either of the following:
a. Reinstall the flowtube in

order to make the arrow and
flow direction match.

b. Reverse the setting for the

flow direction.

Change the piping or the
mounting condition so that
the tube fills with the fluid.

Remove the foreign matter.

START

Contact a service center.

Check the resistance between
the flowtube’s A, B, and C
terminals using a multimeter.

Is the

resistance 100 M

⍀ or more

in each case?

NO

YES

F1008.EPS