Terminal configuration, Terminal wiring – Yokogawa AXFA14G/C User Manual
Page 107
IM 01E20C02-01E
11-5
11. OUTLINE
Signal Cable:
Model
Suffix Code
Description
AXFC
Termination
Cable Length
Option
Magnetic Flowmeter
Dedicated Signal cable for the ADMAG AXF series
No Termination.
A set of termination parts for M4 screws is attached.
Terminated for the AXFA11/14 Remote Converter.
Designate the cable length, unit: m
Following “L”, specify the cable in three digits as
multiple of 1 meter (e.g., 001, 002, or 005) for a
length up to 5 m, or as a multiple of 5 meters
(i.e., 005, 010, 015, or the like).
The maximum cable length:
200 m for combined use with AXFA11
100 m for combined use with AXFA14
With termination parts sets.
Following “C”, specify the q’ty of sets of
termination parts in one digits.
· · · · · · · · · · · · ·
-0 · · · · · · · · · · ·
-4 · · · · · · · · · · ·
-L
ٗٗٗ · · · · ·
/C
ٗ
T04.EPS
Note:
• The cable is constructed with double shielding over the two
conductors, and uses heat-resistant vinyl as the outer covering
material.
Finished diameture: 10.5 mm (0.41 in.)
Maximum temperature: +80˚C (+175˚F)
• Unnecessary to order the above cable for submersible type
flowtube or for the optional code DHC flowtube because the
flowtube is wired with 30 m (98 ft) cable.
• For excitation cable, prepare a two-core cable at the customer side.
● Terminal Configuration “᭛”
SB
B
A
SA
C
EX2
EX1
DIO-
DIO+
DO-
DO+
I-
I+
L/+
N/-
F05.EPS
● Terminal Wiring “᭛”
T06.EPS
Flow singal
input
Excitation current
Output
Power supply
Current output
4 to 20mA DC
Pulse output/
Alarm output/
Status output
Alarm output/
Status output/
Status input
Functional grounding
Terminal
Symbols
Description
EX1
EX2
C
SA
A
B
SB
Terminal
Symbols
Description
N/–
L/+
I+
I–
DO+
DO–
DIO+
DIO–
Protective grounding
(Outside of the terminal)