Function Group 4: Digital Display Modes
Function
No. Description
Range/Code
Factory
Setting
User
Setting
4.00
Display Mode
0000: Frequency
0001: RPM
(1)
0002: Custom Units (Default is "0100")
0000
4.01
Custom Units (Significant Digits)
0 – 9999
100
4.02
Custom Units Display
0000: Whole Numbers (XXXX)
0001: One Decimal Place (XXX.X)
0002: Two Decimal Places (XX.XX)
0003: Three Decimal Places (X.XXX)
0000
4.03
Display in Stop Mode
0000: Displays Last Run Setting
0001: Displays "Stop"
0002: Displays "0000"
0000
4.04
Motor Current Display
(2, 3)
0000: Disabled
0001: Enabled
0000
4.05 Motor
Voltage
Display
(2, 3)
0000: Disabled
0001: Enabled
0000
4.06
Bus Voltage Display
(2, 3)
0000: Disabled
0001: Enabled
0000
4.07–412 Reserved
—
— —
Notes: (1) Based on 4-pole motor. (2) The Display Key is used to toggle between displays.
(3) If Motor Current Display is enabled, the display will show "XX.XA". If Motor Voltage Display is
enabled, the display will show "XXXu". If Bus Voltage Display is enabled, the display will show
"XXXU". If Motor Torque Output is enabled, the display will show "XXXt". If Motor Power Output
is enabled, the display will show "XXXP".
Function Group 5: Multi-Function Output Relay Operating Mode and Output Signal
Operation
Function
No.
Description Range/Code
Factory
Setting
User
Setting
5.00
Multi-Function Output Relay 1
(TB2 on Drive)
0000
5.01
Multi-Function Output Relay 2
(1)
(TB3 on IODF)
0001
5.02
Multi-Function Open Collector Output
(1)
(Terminal 13 of TB1 on IODF)
0000: Run
0001: Fault
(2)
0002: Target Frequency (5.03 ± 5.04)
0003: Frequency Threshold Level
(>
5.03
–
5.04)
(3)
0004: Frequency Threshold Level
(<
5.03
+
5.04)
(4)
0005: I
2
t or I•t Fault
0006: Load Loss (See 5.05)
(5)
0007: External Fault
0005
5.03
Frequency Reached (Hz)
0.00 – 240.0
0.00
5.04
Frequency Bandwidth (± Hz)
0.00 – 30.00
1.00
5.05
Load Loss Threshold
(5)
(% Motor Current, Set by Function
0.01)
25 – 90
60
5.06–5.13 Reserved
—
— —
5.14
Analog Output 1 Mode
(Terminals 11, 12) (0 – 5 Volts DC)
0000: Output Frequency
0001: Set Frequency
0002: Motor Voltage
0003: Bus Voltage
0004: Motor Current
0000
5.15
Analog Output 1 Gain (%)
0 – 200
100
Note: (1) IODF Option Board required. (2) The Multi-Function Output Relay contacts and Open
Collector Outputs will change state due to all Faults and Recovered Faults. (3) The Multi-
Function Output Relay contacts and Open Collector Outputs will activate above the setting in
Function 5.03 and deactivate below the setting in Function 5.03 minus the setting in Function
5.04. (4) The Multi-Function Output Relay contacts and Open Collector Outputs will activate
below the setting in Function 5.03 and deactivate above the setting in Function 5.03 plus the
setting in Function 5.04. (5) The Load Loss Threshold function is not functional during
acceleration/deceleration or Stop Mode.