KB Electronics KBDF-48 User Manual
Page 41
41
FIGURE 32
ACCEL/DECEL #2
CONNECTIONS AND DRIVE PROGRAMMING
*Factory setting.
8.4.4 MULTI-FUNCTION OUTPUT RELAY
The Multi-Function Output Relay connections are located on TB2,
as shown in Figure 33. To access TB2, remove the drive's cover.
See Section 8.4, on page 25.
The Multi-Function Output Relay is factory programmed to
function as a "Run" Relay (Function 5.00 set to "0000"). When
the drive is put into the Run Mode, the relay contacts will change
state (the Normally Open (N.O.) contact will close and the
Normally Closed (N.C.) contact will open). See Table 9. See
Function 5.00, on page 58, for other modes of operation.
For an additional Multi-function Output Relay, install the optional IODF Input/Output Multi-
Function Expansion Module (Part No. 9646). See Function 5.01, on page 58.
TABLE 9
DRIVE MULTI-FUNCTION OUTPUT RELAY "RUN" AND "FAULT" OPERATING MODES
"Run" Relay Mode
(Function 5.00 Set to "0000")
"Fault Relay Mode
(Function 5.00 Set to "0001")
Drive Operating
Condition
N.O. Contact
N.C. Contact
N.O. Contact
N.C. Contact
Power Off
Open
Closed
Open
Closed
Power On (Stop Mode)
Open
Closed
Closed
Open
Run Mode
Closed
Open
closed
Open
All Faults
Open
Closed
Open
Closed
Other Programmable Functions of the Multi-Function Output Relay (Function 5.00)
Code Description
0000: Run
0001: Fault
0002: Target Frequency (Function 5.03 ± Function 5.04)
0003: Frequency Threshold Level (>Function 5.03 – Function 5.04)
0004: Frequency Threshold Level (
2
t or I•t Fault
0006: Load Loss (See Function 5.05)
0007: External Fault
Program Function
Setting
1.00: Run/Stop-Forward/Reverse Control
0001: External Contacts*
7.04: Multi-Function Input Terminal 5 (TB1 Term. 9)
0005: Accel/Decel #2
7.16: Accel/Decel #2 Time (Seconds)
0.3 – 180.0 Seconds (10 Seconds*)
FIGURE 33
MULTI-FUNCTION
OUTPUT RELAY
CONNECTIONS