KB Electronics KBDF-48 User Manual
Page 25
25
8.4 REMOTE OPERATION
The Drive is designed with a removable cover to access the Multi-Function Inputs and Outputs
and jumpers to set up the drive for remote operation. It also allows access to install the optional
accessories. See Table 6. Also see Table 7, on page 26.
To remove the cover, press on the finger grips on both side corners of the cover until the
retaining clips disengage from the base and lift it up.
After mounting the drive, setting the jumpers, and all connections are complete, replace the
cover by inserting the tab into the slot on the drive and gently pressing down on the cover until it
snaps into place.
IMPORTANT: For remote operation of the drive, both a Start Command and a Frequency
Command must be given.
Application Notes:
1. For additional programmable Multi-Function Inputs and Output install the Optional IODF
Input/Output Multi-Function Expansion Module (Part No. 9646). The IODF mounts onto the drive
under the front cover. See Appendix A, on page 64.
2. DIDF For direct communication between the drive and Modbus RTU protocol, install the
optimal DIDF RS-232 and RS-485 Modbus RTU Communication Module (Part No. 9647). See
Appendix B, on page 67.
TABLE 6
DRIVE MULTI-FUNCTION INPUT TERMINAL, FUNCTION,
AND FACTORY CODE ASSIGNMENT
Location
Drive IODF
Multi-Function
Input Terminal*
1 2 3 4 5 6 7
Number On
Terminal Block
5 6 7 8 9 14
15
Function
7.00 7.01 7.02 7.03 7.04 7.05 7.06
Factory Code
Setting
0000 0001 0002 0009 0010 0003 0004
Code
Description
Preset
Frequency
Operation
Preset
Frequency
Operation
Preset
Frequency
Operation
Reset N.O.
Start
Up
Frequency
Command
Down
Frequency
Command
*Each Multi-Function Input Terminal is controlled by a specific Function. Although factory set to
a specific code, they can also be reprogrammed to any code "0000" – "0012" listed in Table 7,
on page 26. Also see Function Group 7, on page 60.