14
TABLE 2
GENERAL PERFORMANCE SPECIFICATIONS
Description Specification
Factory
Setting
115 Volt AC Line Input Operating Range
(Volts AC, 50/60 Hz)
115 (± 15%)
──
208/230 Volt AC Line Input Operating Range
(Volts AC, 50/60 Hz)
208 (-15%) / 230 (+15%)
──
400/460 Volt AC Line Input Operating Range
(Volts AC, 50/60 Hz)
380 (-15%) – 460 (+15%)
──
Maximum Load
(% of Current Overload for 2 Minutes)
150
──
Switching Frequency
(kHz)
8, 10, 12, 14, 16
8
Voltage Following Signal Input Range
(Volts DC)
0 – ±5, 0 ±10
0 – 5
Current Following Signal Input Range
(mA DC)
4 – 20, 0 – 20
──
PWM Following Signal Input Range
(kHz / % Duty Cycle)
0.15 – 1 / 0 - 100
──
Analog Output
(Volts DC)
0 – 5
──
Output Frequency Resolution
(Hz)
0.06
──
Minimum Operating Frequency at Motor
(Hz)
0.3
──
Acceleration Time
(Seconds)
0.1 – 180.0
1.5
Deceleration Time
(Seconds)
0.3 – 180.0
1.5
Speed Range
(Ratio)
50:1
──
Speed Regulation (30:1 Speed Range, 0 – Full Load)
(% Base Speed)
1
2.5
──
Overload Protector Trip Time for Stalled Motor (Seconds)
6
──
115 Volt AC Line Input
Undervoltage/Overvoltage Trip Points (± 5%) (Volts AC)
2
76 – 141
──
208/230 Volt AC Line Input
Undervoltage/Overvoltage Trip Points (± 5%) (Volts AC)
2
151 – 282
──
400/460 Volt AC Line Input
Undervoltage/Overvoltage Trip Points (± 5%) (Volts AC)
2
302 / 567
──
Multi-Function Relay Output Contact Rating
(Amps at 30 Volts DC, 125 Volts AC, 250 Volts AC)
1, 0.5, 0.25
──
Operating Temperature Range
(°C / °F)
0 – 40 / 32 – 104
──
Operating Humidity Range
(% Relative, Non-Condensing)
0 – 95
──
Storage Temperature
(°C / °F)
-25 – +85 / -13 – +185
──
Notes: 1. Dependent on motor performance. 2. Do not operate the drive outside the specified
AC Line input voltage operating range.