KB Electronics KBDF-48 User Manual
Page 57
57
Function Group 2: Frequency Control
Function
No. Description
Code
Factory
Setting
User
Setting
2.00 * Local Frequency Control
0000: Keypad
0001: Built-In Potentiometer
0000
2.01 * Remote Frequency Control**
0000: Analog Signal 1
0001: Analog Signal 2
(1)
0002: Communication
(2)
0003: Up/Down Using MFITs
0000
2.02 * Up Key, Down Key Operation Mode
0000: Frequency Change Requires
Enter
Command
0001: Direct Frequency Change
0002: Keypad Disable
0000
2.03 * Local/Remote Key Operation
0000: Local/Remote Enabled
(Frequency
Control
and
Run/Stop-Fwd/Rev)
0001: Local/Remote Enabled
(Run/Stop-Fwd/Rev
Only)
0002: Local Mode Disabled
0003: Remote Mode Disabled
0000
Notes: (1) IODF Option Board required. (2) DIDF Option Board required.
*Functions which can only be changed while the drive is in the Stop Mode.
**Preset Frequency Operation is performed using the Multi-Function Input Terminals.
Function Group 3: Drive Operating Parameters
Function
No.
Description Range/Code
Factory
Setting
User
Setting
3.00
Stored Set Frequency (Hz)
0.00 – 240.0
5.00
3.01
Lower Frequency Limit (Hz)
0.00 – 240.0
0.00
3.02
Upper Frequency Limit (Hz)
(1)
0.00 – 240.0
60.0, 50.0
3.03
Accel Time (Seconds)
(2)
0.1 – 180.0
1.5
3.04
Decel Time (Seconds)
(2)
0.3 – 180.0
1.5
3.05
S-Curve Time Accel (Seconds)
(2)
0.0 – 30.0
0.0
3.06
S-Curve Time Decel (Seconds)
(2)
0.0 – 30.0
0.0
3.07 * Skip Frequency (Hz)
0.00 – 240.0
0.00
3.08 * Skip Frequency Bandwidth (± Hz)
0.00 – 2.00
0.00
3.09 * Motor Overload Protection
0000: I
2
t with Current Limit
(CL is 160% of Function 0.01)
0001: I•t with Current Limit
(CL is 120% of Function 0.01)
0000
3.10 *
I•t with Current Limit Trip Time
(Seconds)
1.0 – 20.0
6.0
3.11–3.12 Reserved
—
— —
3.13 Boost
Mode
0000: Auto
0001: Fixed (See 3.14)
0000
3.14 Boost
Value
(%)
0.0 – 28.0
7.0
3.15 * Switching Frequency (kHz)
0000: 8
0001: 10
0002: 12
0000
3.16
Flux Vector Compensation (%)
0.0 – 10.0
5.0
3.17 Reserved
—
— —
3.18 Fan
Control
(3)
0000: Auto Run (Temperature Control)
0001: Run Mode Only
0002: Run Continuously
0003: Fan Off
0000
3.19–3.24 Reserved
—
— —
Notes: (1) When the drive is set for 50 Hz motors (Function 0.00 set to code "0001"), the Upper
Frequency Limit factory setting will automatically reset to 50 Hz. (2) Time set for Functions 3.03
and 3.04 must be equal to or greater than the time set for Functions 3.05 and 3.06, respectively.
(3) Models with fan installed only.
*Functions which can only be changed while the drive is in the Stop Mode.