Linearization Menu
The X96S is capable of performing a multi-point linearization of the weight data when required by an application. The
linearization table contains thirty entries, numbered 1 through 30. Each entry consists of a measured value, an actual value, and a
flag that indicates if the entry is used
2
.
The Linearization menu is used to control the linearization mechanism. It contains the following items:
ITEM
FUNCTION
Linearize
Shows the current state of the Linearization mechanism (enabled or disabled) and
allows the user to change the state.
Clear Table
This item invokes a method that clears all entries in the linearization table
Config Linearize
Selecting this item takes the user to the Config Linearize menu
Config Linearize Menu
The Config Linearize menu is used to configure the parameters associated with linearization of the measured data. It contains
the following items:
ITEM
FUNCTION
Table Entry #
Shows, and allows the user to select, an entry in the linearization table
Entry Used
Shows if the entry is used or not.
Measured
Shows, and allows the user to set, the measured value associated with this linearization
table entry. This is the nonlinear value calculated by the X96S when linearization is
disabled.
Actual
Shows, and allows the user to set, the actual value associated with this linearization
table entry. This value is the result of actual level knowledge, and compares to the
Measured value above.
Set Entry
This item invokes a method that sets a table entry
Remove Entry
This item invokes a method that removes a table entry
Scan Time Menu
The
Scan Time
menu is used to configure the rate the input board scans the detector signal and the rate the microprocessor
updates the LCD display and the output signal.
2
Not all of the entries need to be used and the entries do not need to be used in any particular order.