beautypg.com

F-cim 74 setpoint generator - 3, Will equal s – Micromod Micro-DCI: 53MC5000 Multi-Loop Process Controller CUSTOMIZATION GUIDE User Manual

Page 76

background image

F-CIM 74
SETPOINT GENERATOR - 3

NOT REUSABLE

NAME

SYMBOL

DATAPOINT

INPUTS

S

n-1

REMOTE SETPOINT

RSP3

C228

A

REMOTE SP ENABLE

RE3

L187

B

SETPOINT TRACK INPUT

STV3

C236

C

SETPOINT TRACK SWITCH

SWSPT3

L188

PARAMETERS

SETPOINT TRACK ENABLE

STE3

L190

REMOTE GAIN

K13

C221

REMOTE BIAS

B13

C220

INSTRUMENT RANGE

IR3

C223

SETPOINT HI LIMIT

SH3

C233

SETPOINT LOW LIMIT

SL3

C234

OUTPUTS

S

n

SETPOINT

SP3

C209

SETPOINT TRACK STATUS

SPTS3

L176

REMOTE STATUS

RMT3

L180

REMOTE SWITCH

SWR3

L185

Description:
This module selects one of three signals to load into SP and become its output
(S

n

). The signal selected is either the Setpoint Tracking Value (B), the Remote

Setpoint Value (S

n-1

) multiplied by K1 and biased by B1, or the Setpoint pushbut-

ton value. If the Setpoint Track Switch (C) is less than 1, then S

n

=B when Setpoint

Tracking is enabled (STE=1). When the previous condition is not in effect S

n

will

equal S

n-1

x K1 + B1 if RemoteEnable (A) is greater than or equal to 1 and the

R/L pushbutton has set Remote Switch to1. When none of the previous conditions
are in effect the selected signal comes directly from the setpoint increase and de-
crease pushbuttons.

MODULAR CONTROLLER CUSTOMIZATION GUIDE

3-24