beautypg.com

G08 pid - 0 – Micromod Micro-DCI: 53MC5000 Multi-Loop Process Controller CUSTOMIZATION GUIDE User Manual

Page 38

background image

G08

PID - 0

NAME

SYMBOL

DATAPOINT

INPUTS

PROCESS VARIABLE

PV0

C100

DEVIATION

DV0

C121

RESET FEEDBACK

RF0

C127

CONTROL TRACK
COMMAND

CTC0

L123

PARAMETERS

PROPORTIONAL BAND

PB0

C106

RESET TIME

TR0

C107

RATE TIME

TD0

C108

OUTPUT HIGH LIMIT

OH0

C109

OUTPUT LOW LIMIT

OL0

C110

MANUAL RESET

MR0

C111

INSTRUMENT RANGE

IR0

C115

FEED FORWARD

FF0

C122

REVERSE SWITCH

RSW0

L106

OUTPUTS

CONTROL OUTPUT

CO0

C123

Description:
This subroutine computes a control output signal based on the above listed inputs
and parameters. The result is available as a database parameter CO. When the
control track command is zero,the module output will track the reset feedback by
back calculating the integrator term. When CTC is 1, the reset feedback is used by
the integrator to calculate the next output and should reflect the value (scaled
0-100%) of the value of the final control element. For standard PID controller
operation, reset feedback should equal OUT and control track command should
equal AUT.

MODULAR CONTROLLER CUSTOMIZATION GUIDE

2-31