F-CIM 67

DEVIATION/ALARM CALCULATION - 2

NOT REUSABLE

INPUTS

NAME

SYMBOL

DATAPOINT

S

n-1

SETPOINT

SP2

C173

A

PROCESS VARIABLE

PV2

C172

PARAMETERS

SETPOINT SLEW RATE

T12

C189

CONTROL ZONE

C22

C186

ALARM INDEX

AIX2

B345

ALARM LIMIT 1

PL12

C175

ALARM LIMIT 2

PL22

C176

ALARM DEADBAND

ADB2

C177

OUTPUTS

S

n

DEVIATION

DV2

C193

ALARM A

PA12

L158

ALARM B

PA22

L159

TRUE SETPOINT

TSP2

C191

Description:
This module calculates and loads the deviation value based on setpoint (S

n

) and

process variable (A). Before the calculation is performed the setpoint value is con-
ditioned so as not to exceed the rate of change limit specified by T1. If the calcu-
lated deviation falls within the CZ value, then deviation is forced to 0.0. This
module also determines if alarm conditions exist based on AIX, PL1, PL2 and
ADB. Results of the alarm tests are loaded to PA1 and PA2. Refer to Section
4.1.6 of Instruction Bulletin 53MC5000 for an explanation of AIX values.

MODULAR CONTROLLER CUSTOMIZATION GUIDE

3-21