beautypg.com

F-cim 73 auto/manual switch - 3, Will equal s – Micromod Micro-DCI: 53MC5000 Multi-Loop Process Controller CUSTOMIZATION GUIDE User Manual

Page 75

background image

F-CIM 73

AUTO/MANUAL SWITCH - 3

NOT REUSABLE

INPUTS

NAME

SYMBOL

DATAPOINT

S

n-1

CONTROL OUTPUT

CO3

C231

A

AUTO ENABLE

AE3

L186

B

OUTPUT TRACK VALVE

OTV3

C237

C

OUTPUT TRACK SWITCH

SWOTV3

L189

PARAMETERS

OUTPUT TRACK ENABLE

OTE3

L191

HARD MANUAL LIMIT

HML3

L194

OUTPUT HIGH LIMIT

OH3

C217

OUTPUT LOW LIMIT

OL3

C218

OUTPUT SLEW RATE

T33

C226

OUTPUTS

S

n

OUTPUT

OUT3

C210

OUTPUT TRACK STATUS

OVTS3

L177

AUTO STATUS

AUT3

L179

Description:
This module selects one of three signals to load into OUT and become its output
(S

n

). The signal selected is either the Output Tracking Value (B), the Auto Value

(S

n-1

) or the Manual Pushbutton Value. If the Output Tracking Switch (C) is less

than 1, then S

n

= B when Output Tracking is enabled (OTE = 1). When the pre-

vious condition is not in effect S

n

will equal S

n-1

if Auto Enable (A) is

≥ 1 and the

A/M pushbutton has set the Auto Switch to 1. When neither previous condition is
in effect the selected signal comes directly from the output increase and decrease
pushbuttons.

MODULAR CONTROLLER CUSTOMIZATION GUIDE

3-23