G09
PID - 1

NAME

SYMBOL

DATAPOINT

INPUTS

PROCESS VARIABLE

PV1

C136

DEVIATION

DV1

C157

RESET FEEDBACK

RF1

C163

CONTROL TRACK
COMMAND

CTC1

L147

PARAMETERS

PROPORTIONAL BAND

PB1

C142

RESET TIME

TR1

C143

RATE TIME

TD1

C144

OUTPUT HIGH LIMIT

OH1

C145

OUTPUT LOW LIMIT

OL1

C146

MANUAL RESET

MR0

C147

INSTRUMENT RANGE

IR1

C151

FEED FORWARD

FF1

C158

REVERSE SWITCH

RSW1

L130

OUTPUTS

CONTROL OUTPUT

CO1

C159

Description:
This subroutine computes a control output signal based on the above listed inputs
and parameters. The result is available as a database parameter CO. When the
control track command is zero,the module output will track the reset feedback by
back calculating the integrator term. When CTC is 1, the reset feedback is used by
the integrator to calculate the next output and should reflect the value (scaled
0-100%) of the value of the final control element. For standard PID controller
operation, reset feedback should equal OUT and control track command should
equal AUT.