beautypg.com

F-cim 53 auto/manual switch - 1, Will equal s – Micromod Micro-DCI: 53MC5000 Multi-Loop Process Controller CUSTOMIZATION GUIDE User Manual

Page 66

background image

F-CIM 53
AUTO/MANUAL SWITCH - 1

NOT REUSABLE

INPUTS

NAME

SYMBOL

DATAPOINT

S

n-1

CONTROL OUTPUT

CO1

C159

A

AUTO ENABLE

AE1

L138

B

OUTPUT TRACK VALVE

OTV1

C165

C

OUTPUT TRACK SWITCH

SWOTV1

L141

PARAMETERS

OUTPUT TRACK ENABLE

OTE1

L143

HARD MANUAL LIMIT

HML1

L146

OUTPUT HIGH LIMIT

OH1

C145

OUTPUT LOW LIMIT

OL1

C146

OUTPUT SLEW RATE

T31

C154

OUTPUTS

S

n

OUTPUT

OUT1

C138

OUTPUT TRACK STATUS

OVTS1

L129

AUTO STATUS

AUT1

L131

Description:
This module selects one of three signals to load into OUT and become its output
(S

n

). The signal selected is either the Output Tracking Value (B), the Auto Value

(S

n-1

) or the Manual Pushbutton Value. If the Output Tracking Switch (C) is less

than 1, then S

n

= B when Output Tracking is enabled (OTE = 1). When the pre-

vious condition is not in effect S

n

will equal S

n-1

if Auto Enable (A) is

≥ 1 and the

A/M pushbutton has set the Auto Switch to 1. When neither previous condition is
in effect the selected signal comes directly from the output increase and decrease
pushbuttons.

MODULAR CONTROLLER CUSTOMIZATION GUIDE

3-14