beautypg.com

G14 auto/manual switch - 2 – Micromod Micro-DCI: 53MC5000 Multi-Loop Process Controller CUSTOMIZATION GUIDE User Manual

Page 44

background image

G14

AUTO/MANUAL SWITCH - 2

INPUTS

NAME

SYMBOL

DATAPOINT

CONTROL OUTPUT

CO2

C195

AUTO ENABLE

AE2

L162

OUTPUT TRACK VALVE

OTV2

C201

OUTPUT TRACK SWITCH

SWOTV2

L165

PARAMETERS

OUTPUT TRACK ENABLE

OTE2

L167

HARD MANUAL LIMIT

HML2

L170

OUTPUT HIGH LIMIT

OH2

C181

OUTPUT LOW LIMIT

OL2

C182

OUTPUT SLEW RATE

T32

C190

OUTPUTS

OUTPUT

OUT2

C174

OUTPUT TRACK STATUS

OVTS2

L153

AUTO STATUS

AUT2

L155

Description:
The AUTO/MAN Switch selects one of three signals to load into OUT. The signal
selected is either the Output Tracking Value (OTV), the Auto Value (CO) or the
Manual Pushbutton Value. If the Output Tracking Switch (SWOUT) is zero (0) then
OUT = OTV when Output Tracking is enabled (OTE = 1). When the previous
condition is not in effect OUT will equal CO if Auto Enable = 1 and the A/M
pushbutton has set the Auto Switch to 1. When neither previous condition is in effect
the selected signal comes directly from the output increase and decrease pushbut-
tons.

MODULAR CONTROLLER CUSTOMIZATION GUIDE

2-37