beautypg.com

F-cim 61 pid - 2 – Micromod Micro-DCI: 53MC5000 Multi-Loop Process Controller CUSTOMIZATION GUIDE User Manual

Page 69

background image

F-CIM 61

PID - 2

NOT REUSABLE

NAME

SYMBOL

DATAPOINT

INPUTS

S

n-1

DEVIATION

DV2

C193

A

[unused]

B

RESET FEEDBACK

RF2

C199

C

CONTROL TRACK COM-
MAND

CTC2

L171

PARAMETERS

PROPORTIONAL BAND

PB2

C178

RESET TIME

TR2

C179

RATE TIME

TD2

C180

OUTPUT HIGH LIMIT

OH2

C181

OUTPUT LOW LIMIT

OL2

C182

MANUAL RESET

MR2

C183

INSTRUMENT RANGE

IR2

C187

FEED FORWARD

FF2

C194

REVERSE SWITCH

RSW2

L154

OUTPUTS

S

n

CONTROL OUTPUT

CO2

C195

Description:
This module computes a control output signal based on the above listed inputs and parameters.

The result is simultaneously available as the module output S

n

and as a database parameter

CO. The A, B, and C inputs can be any L,B, C[S], or H type datapoint. When the
control track command input is less than one, the module output will track the reset
feedback input (B)by back calculating the integrator term. When (C) input is greater
than or equal to 1 the reset feedback is used by the integrator to calculate the next
output and should reflect the value (scaled 0-100%) of the value of the final control
element. For standard PID controller reset feedback, (B) should be OUT and con-
trol track command should be AUT.

MODULAR CONTROLLER CUSTOMIZATION GUIDE

3-17