F-CIM 44
SETPOINT GENERATOR - 0

NOT REUSABLE

NAME

SYMBOL

DATAPOINT

INPUTS

S

n-1

REMOTE SETPOINT

RSP0

C120

A

REMOTE SP ENABLE

RE0

L115

B

SETPOINT TRACK INPUT

STV0

C128

C

SETPOINT TRACK SWITCH

SWSPT0

L116

PARAMETERS

SETPOINT TRACK ENABLE

STE0

L118

REMOTE GAIN

K10

C113

REMOTE BIAS

B10

C112

INSTRUMENT RANGE

IR0

C115

SETPOINT HI LIMIT

SH0

C125

SETPOINT LOW LIMIT

SL0

C126

OUTPUTS

S

n

SETPOINT

SP0

C101

SETPOINT TRACK STATUS

SPTS0

L104

REMOTE STATUS

RMT0

L108

REMOTE SWITCH

SWR0

L113

Description:
This module selects one of three signals to load into SP and become its output (Sn). The signal se-
lected is either the Setpoint Tracking Value (B), the Remote Setpoint Value (Sn-1) multiplied by K1
and biased by B1, or the Setpoint pushbutton value. If the Setpoint Track Switch (C) is less than 1,
then Sn=B when Setpoint Tracking is enabled (STE=1). When the previous condition is not in ef-
fect Sn will equal Sn-1 x K1 + B1 if RemoteEnable (A) is greater than or equal to 1 and the R/L
pushbutton has set Remote Switch to1. When none of the previous conditions are in effect the se-
lected signal comes directly from the setpoint increase and decrease pushbuttons.

MODULAR CONTROLLER CUSTOMIZATION GUIDE

3-10