beautypg.com

G12 auto/manual switch - 0 – Micromod Micro-DCI: 53MC5000 Multi-Loop Process Controller CUSTOMIZATION GUIDE User Manual

Page 42

background image

G12

AUTO/MANUAL SWITCH - 0

INPUTS

NAME

SYMBOL

DATAPOINT

CONTROL OUTPUT

CO0

C123

AUTO ENABLE

AE0

L114

OUTPUT TRACK VALVE

OTV0

C129

OUTPUT TRACK SWITCH

SWOTV0

L117

PARAMETERS

OUTPUT TRACK ENABLE

OTE0

L119

HARD MANUAL LIMIT

HML0

L122

OUTPUT HIGH LIMIT

OH0

C109

OUTPUT LOW LIMIT

OL0

C110

OUTPUT SLEW RATE

T30

C118

OUTPUTS

OUTPUT

OUT0

C102

OUTPUT TRACK STATUS

OVTS0

L105

AUTO STATUS

AUT0

L107

Description:
The AUTO/MAN Switch selects one of three signals to load into OUT. The signal
selected is either the Output Tracking Value (OTV), the Auto Value (CO) or the
Manual Pushbutton Value. If the Output Tracking Switch (SWOUT) is zero (0) then
OUT = OTV when Output Tracking is enabled (OTE = 1). When the previous
condition is not in effect OUT will equal CO if Auto Enable = 1 and the A/M
pushbutton has set the Auto Switch to 1. When neither previous condition is in effect
the selected signal comes directly from the output increase and decrease pushbut-
tons.

MODULAR CONTROLLER CUSTOMIZATION GUIDE