beautypg.com

F-cim 63 auto/manual switch - 2, Will equal s – Micromod Micro-DCI: 53MC5000 Multi-Loop Process Controller CUSTOMIZATION GUIDE User Manual

Page 71

background image

F-CIM 63

AUTO/MANUAL SWITCH - 2

NOT REUSABLE

INPUTS

NAME

SYMBOL

DATAPOINT

S

n-1

CONTROL OUTPUT

CO2

C195

A

AUTO ENABLE

AE2

L162

B

OUTPUT TRACK VALVE

OTV2

C201

C

OUTPUT TRACK SWITCH

SWOTV2

L165

PARAMETERS

OUTPUT TRACK ENABLE

OTE2

L167

HARD MANUAL LIMIT

HML2

L170

OUTPUT HIGH LIMIT

OH2

C181

OUTPUT LOW LIMIT

OL2

C182

OUTPUT SLEW RATE

T32

C190

OUTPUTS

S

n

OUTPUT

OUT2

C174

OUTPUT TRACK STATUS

OVTS2

L153

AUTO STATUS

AUT2

L155

Description:
This module selects one of three signals to load into OUT and become its output
(S

n

). The signal selected is either the Output Tracking Value (B), the Auto Value

(S

n-1

) or the Manual Pushbutton Value. If the Output Tracking Switch (C) is less

than 1, then S

n

= B when Output Tracking is enabled (OTE = 1). When the pre-

vious condition is not in effect S

n

will equal S

n-1

if Auto Enable (A) is

≥ 1 and the

A/M pushbutton has set the Auto Switch to 1. When neither previous condition is
in effect the selected signal comes directly from the output increase and decrease
pushbuttons.

MODULAR CONTROLLER CUSTOMIZATION GUIDE

3-19