Laurel Electronics LAUREATE SERIES 2 COUNTER-TIMER-SERIAL INPUT METER User Manual

Page 58

background image

58

Press
Menu

Press Digit
Select Key

Press Value Select
Key

00000

Relay alarm state when
alarm is active.

0

Relay 3 active on

Relay 4 active on

1

Relay 3 active off

Relay 4 active on

2

Relay 3 active on

Relay 4 active off

3

Relay 3 active off

Relay 4 active off

00000

Alarm latching or non-
latching (auto reset).
(see Glossary)

0

AL3 non-latching

AL4 non-latching

1

AL3 latching

AL4 non-latching

2

AL3 non-latching

AL4 latching

3

AL3 latching

AL4 latching

00000

Alarm operates at and
above setpoint (active
high) or at and below
setpoint (active low).
(see Glossary)

0

AL3 active high

AL4 active high

1

AL3 active low

AL4 active high

2

AL3 disabled

AL4 active high

3

AL3 active high

AL4 active low

4

AL3 active low

AL4 active low

5

AL3 disabled

AL4 active low

6

AL3 active high

AL4 disabled

7

AL3 active low

AL4 disabled

8

AL3 disabled

AL4 disabled

00000

Hysteresis mode or band
deviation mode
(see Glossary)

0

AL3 band deviation AL4 band deviation

1

AL3 hysteresis

AL4 band deviation

2

AL3 band deviation AL4 split hysteresis

3

AL3 hysteresis

AL4 hysteresis

ALS 34

Alarm Setup
for relays 3 & 4
if detected.

00000

Number of consecutive
readings in alarm zone to
cause an alarm.

0

After 1 reading

4

After 16 readings

1

After 2 readings

5

After 32 readings

2

After 4 readings

6

After 64 readings

3

After 8 readings

7

After 128 readings

Press
Menu

Press Digit
Select Key

Press Value Select
Key

dEUn1H

Alarm 1 hysteresis

DEUn2H

Alarm 2 hysteresis

DEUn1b

Alarm 1 band deviation

DEUn2b

Alarm 2 band deviation

dEUn1h

Alarm 1 span hysteresis

DEUn2h

Alarm 2 span hysteresis

dEUn3H

Alarm 3 hysteresis

DEUn4H

Alarm 4 hysteresis

DEUn3b

Alarm 3 band deviation

DEUn4b

Alarm 4 band deviation

0.00000 0.00000 0.00000
0.00000 0.00000 0.00000

Select digit to flash

Select

-9

thru

9

for flashing

first digit,

0

thru

9

for other

flashing digits. Alarms will
activate above the setpoint
by the value entered and
deactivate below the setpoint
by the value entered. For
span hysteresis, the alarms
will activate (deactivate) at
the setpoint and deactivate
(activate). See Glossary.