beautypg.com

Processpro editing procedure, Step 1, Step 2 – GF Signet 8550 ProcessPro Flow Transmitter User Manual

Page 5: Step 3, Step 4, Step 5, Step 6, Step 3: finished editing, Step 5: made an error

background image

5

Signet 8550-3 Flow Transmitter Instructions

Output1 Setpnt:

2

0.00 GPM

Output1 Setpnt:

1

0.00 GPM

ENTER

Output1 Setpnt:

1

0

.00

GPM

Output1 Setpnt:

1

9

.00 GPM

Output1 Setpnt:

Saving

Output1 Setpnt:

19.00 GPM >

Notes on Steps 5 and 6:
• All output functions remain active during editing.
• Only the fl ashing element can be edited.
• ► key advances the fl ashing element in a continuous loop.
• Edited value is effective immediately after pressing ENTER key.
• If no key is pressed for 10 minutes unit will restore the last saved value and return to step 3.
• Step 6 (pressing ENTER key) always returns you to Step 3.
• Repeat steps 3-6 until all editing is completed.

Notes on Step 2:
If no key is pressed for 5 minutes while display is showing "Enter
Key Code", the display will return to the VIEW menu.

Notes on Steps 3 and 4:
• Refer to pages 6 and 7 for complete listing of menu items and their use.
• From the Step 3 display, pressing the ▲ and ▼ keys simultaneously will return

the display to the VIEW menu.

• If no key is pressed for 10 minutes, display will also return to the VIEW menu.

ProcessPro Editing Procedure:

Step 1.

Press and hold ENTER key:

• 2 seconds to select the CALIBRATE menu.

• 5 seconds to select the OPTIONS menu.

Step 2.

The Key Code is

--- keys in sequence.

• After entering the Key Code, the display will show the fi rst item in the selected menu.

Step 3.

Scroll menu with

or arrow keys.

Step 4.

Press

key to select menu item to be edited.

The

fi rst display element will begin fl ashing.

Step 5.

Press

or keys to edit the fl ashing element.

• ► key advances the fl ashing element.

Step 6.

Press ENTER key to save the new setting and return to Step 3.

2s

5s

ENTER

OPTIONS

CALIBRATE

VIEW

Press &
hold for
access:

Step 5

Step 6

Notes on Step 1:
• The View Menu is normally displayed.
• The CALIBRATE and OPTIONS menus require a KEY CODE.

Step 4

First item in
CALIBRATE menu

Step 3

Step 3: Finished Editing?

Press the ▲ and ▼ keys simultaneously after saving
the last setting to return to normal operation.

Press the ▲ and ▼ keys simultaneously while any
element is fl ashing. This will recall the last saved
value of the item being edited and return you to
Step 3.

Step 5: Made an Error?

20.0 GPM

>

Output1 Setpnt:

GPM

>

Flow1 Units:

CALIBRATE: ----

Enter Key Code

CALIBRATE: *---

Enter Key Code

CALIBRATE: **--

Enter Key Code

CALIBRATE: ***-

Enter Key Code

GPM

>

Flow1 Units: