Signet 8550-3 Flow Transmitter

10

9

8

7

6

5

4

3

2

1

16

15

14

13

12

11

Output 2-

Output 2+

Output 1-

Output 1+

Loop 2-

Loop 2+

System Pwr -

Loop 1 -

System Pwr +

Loop 1 +

AUX

Power -

AUX

Power +

Snsr 2 Gnd

(WHITE)

Snsr 2 IN

(RED)

Snsr 2 V+

(BLACK)

Snsr 1 Gnd

(WHITE)

Snsr 1 IN

(RED)

Snsr 1 V+

(BLACK)

3. Electrical

Connections

Caution:

Failure to fully open terminal jaws before removing wire may permanently damage instrument.

Wiring Procedure
1. Remove 0.5 - 0.625 in. (13-16 mm) of insulation from wire end.
2. Press the orange terminal lever downward with a small screwdriver to open terminal jaws.
3. Insert exposed (non-insulated) wire end in terminal hole until it bottoms out.
4. Release orange terminal lever to secure wire in place. Gently pull on each wire to ensure a good connection.

Wiring Removal Procedure
1. Press the orange terminal lever downward with a small screwdriver to open terminal jaws.
2. When fully open, remove wire from terminal.

2
1

1

15

Ÿ

S

D

2

_

+

Internal open-collector

output circuit

Outputs

Isolation

Terminals 3-6: System Power and Loop Power
12-24 VDC ±10% system power and current loop outputs.
Max. loop impedance:

50 Ω max. @ 12 V
325 Ω max. @ 18 V
600 Ω max. @ 24 V

Terminals 11-16: Flow sensor inputs

Terminals 7-10: Open-collector Outputs
Two transistor outputs, programmable (see CALIBRATE menu) as:

• High or Low setpoint with adjustable hysteresis.
• Pulse based on Volume.
• Frequency based on fl ow rate.

May be disabled (Off) if not used.

Terminals 1 and 2: AUXILIARY power
Used only if the fl ow sensor requires more
than 1.5 mA current. For Signet sensors this
is limited to the following products:
• 2000 • 2507 • 2551 • 2552
• Open-collector Input signals

2.1 Panel

Installation

1. The panel mount transmitter is designed for installation using a 1/4 DIN Punch. For

manual panel cutout, an adhesive template is provided as an installation guide.
Recommended clearance on all sides between instruments is 1 inch.

2. Place gasket on instrument, and install in panel.
3. Slide mounting bracket over back of instrument until quick-clips snap into latches on side

of instrument.

4. To remove, secure instrument temporarily with tape from front or grip from rear of

instrument. DO NOT RELEASE.

Press quick-clips outward and remove.

Output -

Output +

System Pwr
Loop -

System Pwr
Loop +

2

1

4

3

Sensr Gnd

(SHIELD)

Sensr IN

(RED)

Sensr V+

(BLACK)

7

6

5

quick-clips

gasket

panel

terminals

mounting

bracket

latch

Panel Mount
Installation Detail