3. Electrical
Connections
Caution:
Failure to fully open terminal jaws before removing wire may permanently damage instrument.
Wiring Procedure
1. Remove 0.5 - 0.625 in. (13-16 mm) of insulation from wire end.
2. Press the orange terminal lever downward with a small screwdriver to open terminal jaws.
3. Insert exposed (non-insulated) wire end in terminal hole until it bottoms out.
4. Release orange terminal lever to secure wire in place. Gently pull on each wire to ensure a good connection.
Wiring Removal Procedure
1. Press the orange terminal lever downward with a small screwdriver to open terminal jaws.
2. When fully open, remove wire from terminal.
2
1
1
15
S
D
2
_
+
Internal open-collector
output circuit
Outputs
Isolation
Terminals 3-6: System Power and Loop Power
12-24 VDC ±10% system power and current loop outputs.
Max. loop impedance:
50 Ω max. @ 12 V
325 Ω max. @ 18 V
600 Ω max. @ 24 V
Terminals 11-16: Flow sensor inputs
Terminals 7-10: Open-collector Outputs
Two transistor outputs, programmable (see CALIBRATE menu) as:
• High or Low setpoint with adjustable hysteresis.
• Pulse based on Volume.
• Frequency based on fl ow rate.
May be disabled (Off) if not used.
Terminals 1 and 2: AUXILIARY power
Used only if the fl ow sensor requires more
than 1.5 mA current. For Signet sensors this
is limited to the following products:
• 2000 • 2507 • 2551 • 2552
• Open-collector Input signals
2.1 Panel
Installation
1. The panel mount transmitter is designed for installation using a 1/4 DIN Punch. For
manual panel cutout, an adhesive template is provided as an installation guide.
Recommended clearance on all sides between instruments is 1 inch.
2. Place gasket on instrument, and install in panel.
3. Slide mounting bracket over back of instrument until quick-clips snap into latches on side
of instrument.
4. To remove, secure instrument temporarily with tape from front or grip from rear of
instrument. DO NOT RELEASE.
Press quick-clips outward and remove.
Output -
Output +
System Pwr
Loop -
System Pwr
Loop +
2
1
4
3
Sensr Gnd
(SHIELD)
Sensr IN
(RED)
Sensr V+
(BLACK)
7
6
5
quick-clips
gasket
panel
terminals
mounting
bracket
latch
Panel Mount
Installation Detail