Safety positions – Burkert Type 8681 User Manual
Page 78

78
Maintenance, Troubleshooting
18.2. safety positions
safety positions after failure of the electrical or pneumatic auxiliary power:
Operating mode
process valve design
safety positions
after failure of the auxiliary power
electrical
pneumatic
up
down
single-acting
Control function A
air opening
•
spring closing
•
down
down
up
down
single-acting
Control function B
air closing
•
spring opening
•
up
up
up
down
double-acting
Control function I
air opening
•
air closing
•
not defined
not defined
By default, the control head is equipped with solenoid valves in circuit function design C
(Circuit function C: 3/2-way valve; closed in rest position, output A unloaded).
If process valves with several switching positions (e.g. double-seated valves) are connected, the safety positions
of the individual drives can be viewed according to the same logic as for a classical one-seated valve.
safety positions after failure of the bus communication:
AS Interface:
If the watchdog is activated (default), behavior corresponds to the event of a failure of the auxiliary electrical
power, i.e. all solenoid valve outputs are set to "0".
DeviceNet:
See chapter "
12.12.1. Configuration of the Safety Position of Solenoid Valves if Bus Error".
english
Control Head Type 8681