Burkert Type 8681 User Manual
Page 70

70
Position Measuring System
- Then position S2 is taught.
- After that, valve V1 is deactivated. It initiates closing of the process valve.
- Once the process valve is closed (after 15 s maximum), position S1 is displayed by LED.
4. Autotune sequence 1 is complete: positions S1 and S2 have been taught.
In the event that a timeout occurs, the corresponding Autotune function will be exited and switched to
normal operation.
Furthermore, the Teach-In positions will be set to "not taught", i.e. they will blink in the fault color.
autotune 2:
control
effect on the process valve
internal program
error
t2 + t3
autotune mode starts
t2
Autotune 2 starts
Open position
Teach
T2
Valve closing
Activate
V1
Wait period
10s
Closed position
Teach
T1
Valve opens
Deactivate
V1
Valve opens
Wait on position S2
S2
Timeout 15s
autotune mode completed
autotune 3:
control
effect on the process valve
internal program
error
t2 + t3
autotune mode starts
t3
Autotune 3 starts
Closed position
Teach
T1
Valve opens
Activate
V1
Wait period
10s
Open position
Teach
T2
Valve closing
Deactivate
V1
Valve closes
Wait on position S1
S1
Timeout 15s
Open clock valve plate
Activate
V2
Wait period
10s
Clock valve plate
Teach
T3
Valve closing
Deactivate
V2
Valve closes
Wait on position S1
S1
Timeout 15s
autotune mode completed
english
Control Head Type 8681