Burkert Type 8611 User Manual
Page 39
39
ConfigurationLevel
FILT
PARA
KP1
KP2 *
)
TREG *
)
KP_T *
)
INV
TN *
)
TN_T *
)
ZERO
DEAD
DE_T *
)
STRT *
)
BACK
YES
YES
NO
NO
*
)
The display depends on the control variable set in the
MODE menu (see Fig. 15)
Enter filter factor ( 2 - 20)
Zero point shut-off (if default < 2 % of the set-point value range). Display only for
INV = NO
Selection of
controller parameters
KP1, Pproportional coefficient 1
KP2, proportional coefficient 2
Cycle time for controller [s] (display only for
MODE = PVC, 3P – T, 2P – T,)
Reset time [s] (display only for
MODE = SCV, 0 – 10, 4 – 20, 2P – T, 3P – T,)
Dead zone absolute. Unit and display of decimal place analogous to
UNIT.
Proportional coefficient for cascaded temperature control (display only for
MODE = T + F)
Reset time in [s] for cascaded temperature control (display only for
MODE = T + F)
Dead zone absolute for cascaded temperature control (display only for
MODE = T + F).
Definition of start value for manipulated variable
(display only for
MODE = SCV, 0 – 10, 4 – 20, 1P – T, 3P – T)
Effective direction
Not inverted or direct control
Inverted control
Zero point shut-off is deactivated
Zero point shut-off is activated
B_IN
Fig. 21: Operating structure of the configuration level - 7 of 12
Definition of start value for manipulated variable (display only for
MODE =
SCV, 0 – 10, 4 – 20)
english
Type 8611