Assembly, Assembly models – Burkert Type 8611 User Manual
Page 13
13
Assembly
Binary input
Input impedance:
10 kΩ
Response threshold:
3 ... 30 V
Max. frequency:
1 kHz
6.5.2. outputs
Continuous signal
Standard signal 4 - 20 mA
Max. loop resistance:
680 Ω
Precision:
0,5 %
Standard signal 0 - 10 V
Maximum current:
20 mA
Precision:
0,5 %
Discontinuous signal
2 transistor outputs for PWM or
PTM control
Control frequency: 1.2 kHz ... 20 Hz
Max. resolution: 16 bit (depending on
frequency)
Max. current per
unit area:
1.5 A
Switching voltage: 24 V DC
Binary output
Transistor output (PNP) configurable
Max. current per
unit area:
1.5 A
Switching voltage: 24 V DC
Sensor supply:
24 V DC
total load for all outputs:
1,5 a
7.
asseMBly
7.1.
assembly models
attachment to a Bürkert
flow-rate fitting
attachment to a proportional
valve
Bürkert
flow-rate
fitting Type
SO30
installation in a control cabinet
The description of the instal-
lation in a control cabinet and the
device dimensions can be found
in the following chapter “7.3.
Assembly of the control cabinet
english
Type 8611