Assembly

Binary input

Input impedance:

10 kΩ

Response threshold:

3 ... 30 V

Max. frequency:

1 kHz

6.5.2. outputs

Continuous signal

Standard signal 4 - 20 mA
Max. loop resistance:

680 Ω

Precision:

0,5 %

Standard signal 0 - 10 V
Maximum current:

20 mA

Precision:

0,5 %

Discontinuous signal

2 transistor outputs for PWM or
PTM control
Control frequency: 1.2 kHz ... 20 Hz
Max. resolution: 16 bit (depending on

frequency)

Max. current per
unit area:

1.5 A

Switching voltage: 24 V DC

Binary output

Transistor output (PNP) configurable
Max. current per
unit area:

1.5 A

Switching voltage: 24 V DC

Sensor supply:

24 V DC

total load for all outputs:

1,5 a

7.

asseMBly

7.1.

assembly models

attachment to a Bürkert
flow-rate fitting

attachment to a proportional
valve

Bürkert
flow-rate
fitting Type
SO30

installation in a control cabinet

The description of the instal-

lation in a control cabinet and the

device dimensions can be found

in the following chapter “7.3.

Assembly of the control cabinet

model”