beautypg.com

Burkert Type 8611 User Manual

Page 24

background image

24

ElectricalInstallation

terminal block 3

terminal Configuration external circuit

19

GND – Pt 100,
RTD

(0 ... 200 °C)

19

20

Pt 100

20
(

AIN3)

(+) Pt 100,
RTD (power
supply)

21

GND – Analog
input

21

A-GND

22
(

AIN1)

(+) Process
value input
4 - 20 mA /
0 - 10 V

22

21

4 - 20 mA / 0 - 10 V
(source)
A-GND

23

GND – Sensor,
actuating
element

23

GND

24

24 V DC
sensor supply
or actuating
element

24
23

24 V DC - Out (max. 1 A)

GND

terminal Configuration external circuit

25
Supply
of Type
8611
(

DIN3)

Frequency
input 2
(NPN or PNP)
Q

2

for ratio

control (

MODE

=

RATI)

Jumper 2

NPN

PNP

Trans-

mitter

12 or

24

24 V DC

GND

11 or

23

Clock

25

Supply of 8611

25
External
supply
(

DIN3)

Frequency
input 2
(NPN or PNP)
Q

2

for ratio

control
(

MODE =

RATI)

Jumper 2

NPN

PNP

Trans-

mitter

GND

11 or

23

GND

Supply

Clock

25

External supply

26
(

DIN2)

(+) Binary input

26

1, 11 or 23

0 ... 2,7 V

(log. 0)

3 ... 30 V
(log. 1)

max.

1 kHz

GND

english